Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

POWER TRANSFORMERS

TDH, TA, TP, TC, TRP — LV measuring and protection current transformers (60–5000 A)

Low-voltage current transformers for 60–5000 A for metering, network analysis and relay protection. The family includes high-accuracy TDH, busbar TA, split-core TP, TC with a converter and protection TRP, with secondary currents of .../5 A.../1 A and .../250 mA.

TDH (high-accuracy)
60–4000 A; classes 0.2 / 0.2S / 0.5S; secondary .../5.../1.../0.25 A; window Ø20–63 mm; sealable, test report
TA
750–5000 A (and lower); busbars 20×100 … 60×125 mm; classes 0.5 / 1 / 3; certificate
TP (split-core)
75–5000 A; .../5 and .../1 A; busbars 30×30 … 160×80 mm; installation without disconnection
TC (with converter)
50–300 A → 0–20 / 4–20 mA, self-powered

Technical specifications

TDH (high-accuracy)60–4000 A; classes 0.2 / 0.2S / 0.5S; secondary .../5.../1.../0.25 A; window Ø20–63 mm; sealable, test report
TA750–5000 A (and lower); busbars 20×100 … 60×125 mm; classes 0.5 / 1 / 3; certificate
TP (split-core)75–5000 A; .../5 and .../1 A; busbars 30×30 … 160×80 mm; installation without disconnection
TC (with converter)50–300 A → 0–20 / 4–20 mA, self-powered
TRP (protection)window 40–180 mm; 100/5 … 5000/5 A; classes 5P10, 5P20; cast resin
Insulation0.72 kV (operating), test S1–S2 3 kV
Ith / Idyn60 In / 2.5 Ith
Frequency50 / 60 Hz

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

TDH are bushing-type transformers for 60–4000 A with a window of 20–63 mm, which can be sealed and are supplied with a test report. TDH5 125/5A has a 20 mm window for busbars of 15 × 15, 20 × 10 or 25 × 5 mm, a safety factor of 5 and a dynamic current of 2.5 Ith. TA with a closed core are rated for 750–5000 A and busbars from 20 × 100 to 60 × 125 mm; TA400 300/5A gives 5 VA in class 0.5, 10 VA in class 1 and 15 VA in class 3. TP have a split core for 75–5000 A, busbars from 30 × 30 to 160 × 80 mm, a lock in TP-10 and TP-12, and TP8 200/5 has a 60 × 80 mm window, class 3 and 1.5 VA. TC are powered from the measured network and output 0–20 or 4–20 mA at currents of 50–300 A, with a 28–44 mm window and busbars from 40 × 10 to 60 × 12 mm. TRP are cast in resin with a 40–180 mm window. The operating voltage is up to 0.72 kV, and the thermal current is 60 In.

How to choose

First determine the primary current and the size of the busbar or cable. If the supply can be switched off during installation, take TDH for metering or TA for large currents, otherwise TP with a split core. TC are needed when 0–20 or 4–20 mA must be supplied to a controller. For protection relays in panels and cells, TRP from 100/5 to 5000/5 A of classes 5P10 and 5P20 are intended.

Request a price and lead time

TDH, TA, TP, TC, TRP — LV measuring and protection current transformers (60–5000 A). We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How does the split-core TP differ from the TA transformer?

TP with a split core for 75–5000 A is installed without switching off the supply. TA has a closed core and suits installations where the supply can be switched off during installation.

What accuracy classes and burdens does TDH5 125/5A have?

Class 0.2 with a burden of 1.5 VA, class 0.2S with 0.75 VA and class 0.5S with 1.5 VA.

What secondary currents do current transformers of this family have?

TDH are made for .../5 A.../1 A and .../250 mA, TP for .../5 and .../1 A, and TC output a signal of 0–20 or 4–20 mA.

Which current transformer should be used for a protection relay?

TRP in cast resin, classes 5P10 and 5P20, ratios from 100/5 to 5000/5 A. TRP40 200/5A 5P20 has a rating of 10 VA.

What are the operating voltage and frequency of these current transformers?

The operating voltage is up to 0.72 kV, the frequency 50/60 Hz, and the test voltage between terminals S1–S2 is 3 kV.

Similar products

Power transformers

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.