TE15P / TE15PR / TE108 / TE150 — measuring voltage transformers up to 1000 V

The TE15P, TE15PR, TE108 and TE150 measuring voltage transformers step down the voltage of networks up to 1000 V and galvanically isolate voltmeters, analyzers, meters, voltage relays and synchronizing devices from it. They are installed in 690 V networks, on ships and in generator and synchronizing panels.

TE15P / TE15PR
primary up to 440 V; secondary 110–230 V; class 0.5 (15 VA) and 1 (25 VA); plastic / resin; IEC/UNE-EN 61869-3
TE108
primary up to 1000 V; secondary 100, 110, 230, 400 V; class 0.2–0.5; 6/25/40 VA; insulation up to 6 kV
TE150
primary 800/√3 V; two secondary windings 100/√3 V: cl. 0.2 (7.5 VA) and cl. 0.5 (5 VA); insulation 3 kV 1 min; weight 11.2 kg
Continuous overload
1.2 Un

Technical specifications

TE15P / TE15PRprimary up to 440 V; secondary 110–230 V; class 0.5 (15 VA) and 1 (25 VA); plastic / resin; IEC/UNE-EN 61869-3
TE108primary up to 1000 V; secondary 100, 110, 230, 400 V; class 0.2–0.5; 6/25/40 VA; insulation up to 6 kV
TE150primary 800/√3 V; two secondary windings 100/√3 V: cl. 0.2 (7.5 VA) and cl. 0.5 (5 VA); insulation 3 kV 1 min; weight 11.2 kg
Continuous overload1.2 Un
Operating range80–120 % Un
Functional load25–100 % (cos φ = 0.8)
Frequency50–60 Hz
Operating temperature−10…+70 °C
StandardsIEC 61869-1/-3, IEC 60185, IEC 61010, VDE 0414, DIN 57414, BS 3938

Replacement for

NOS-0.5, NTS-0.5 (voltage transformers up to 0.5 kV); OSM1 (supply)

selected by purpose and main parameters, please confirm with the manager

Replacement pages: НОС-0,5, НОС, НТС-0,5, НТС

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The TE15P is made in a plastic housing, the TE15PR is resin-encapsulated and has a CE declaration; both accept up to 440 V and deliver 110 to 230 V with class 0.5 at 15 VA or class 1 at 25 VA under IEC/UNE-EN 61869-3. The TE108 with insulation up to 6 kV is used where there is a significant potential difference between circuits; it accepts up to 1000 V, delivers 100, 110, 230 or 400 V at 6, 25 or 40 VA and holds class 0.2 or 0.5. The TE150 has a primary winding of 800/√3 V and two independent secondaries of 100/√3 V each: the first of class 0.2 at 7.5 VA for critical measurements and the second of class 0.5 at 5 VA for auxiliary instruments or supervision. Its insulation is tested with 3 kV for 1 min, and the unit weighs 11.2 kg. The whole series withstands a continuous overload of 1.2 Un and works at 80–120 % Un, a functional load of 25–100 % with cos φ = 0.8, a frequency of 50–60 Hz and a temperature of −10…+70 °C, and is stored at −20…+85 °C and humidity up to 95 %.

How to choose

The first criterion is the primary voltage of the network. Up to 440 V the TE15P or the encapsulated TE15PR is enough, and when class 0.2 or secondaries of 100 or 400 V are needed, the TE108 is suitable. For accurate measurement and an auxiliary circuit from one unit, the TE150 is intended. For the current circuits of the same panels there are cast current transformers TU_R at 25–6000 A, plastic TU_ / TUC_ / TL_ at 50–6000 A and split-core TA_P at 20–5000 A.

Request a price and lead time

TE15P / TE15PR / TE108 / TE150 — measuring voltage transformers up to 1000 V. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How does the TE15P voltage transformer differ from the TE15PR?

Electrically they are the same. The TE15P is assembled in a plastic housing, while the TE15PR is resin-encapsulated, and the CE declaration is issued for it.

Which voltage transformer suits a 690 V network?

The TE108 with a primary voltage up to 1000 V is suitable; the 440 V TE15P is too small for such a network.

Can one voltage transformer feed both metering and protection?

Yes, the TE150 has two independent secondary windings of 100/√3 V, class 0.2 at 7.5 VA and class 0.5 at 5 VA, so a second transformer in the cabinet is not needed.

Which standards do the TE voltage transformers comply with?

The series is built to IEC 185/60185, UNE-EN 61869-1 and 61869-3, IEC 61010, EN 50081/50082, UNE-EN 61000-6-1/-6-3, VDE 0414, DIN 57414 and BS 3938. The materials meet UL94-V0 for flammability.

Similar products

Power transformers

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.