Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

THYRISTOR POWER CONTROLLERS

Thyro-PX — digital thyristor power controller, 1/2/3 phases, 16–5000 A, up to 1000 V

Thyro-PX, the family's senior series, controls power at 16–5000 A and up to 1000 V with ±0.5 % accuracy for voltage or current. It goes on furnaces in the glass, metallurgical and ceramics industries, on heaters with a large resistance spread and on transformer-fed loads.

Phases
1PX — 1 phase; 2PX — 3-phase load in 2-phase circuit; 3PX — 3 phases
Rated current 1PX, 500 V
16, 37, 75, 110, 130, 170, 280, 350, 495, 650, 780, 1000, 1500, 2100, 2900, 5000 A
Rated current 1PX, 690 V
80, 200, 300, 500, 600, 780, 1400, 2000 A
Mains voltage
500 V type: 230 V −20 %…500 V +10 %; 690 V type: 500 V −20 %…690 V +10 %; up to 1000 V

Technical specifications

Phases1PX — 1 phase; 2PX — 3-phase load in 2-phase circuit; 3PX — 3 phases
Rated current 1PX, 500 V16, 37, 75, 110, 130, 170, 280, 350, 495, 650, 780, 1000, 1500, 2100, 2900, 5000 A
Rated current 1PX, 690 V80, 200, 300, 500, 600, 780, 1400, 2000 A
Mains voltage500 V type: 230 V −20 %…500 V +10 %; 690 V type: 500 V −20 %…690 V +10 %; up to 1000 V
Frequency45–65 Hz
ModesTAKT, VAR, VSC (sequential voltage control), soft start/stop
Control typesU, U², I, I², P, no control
Accuracy±0.5 % voltage or current, ±1 % power
Loadresistive, transformer, Rhot/Rcold up to 20 (MOSI start)
Setpoint and outputsup to 3 analog inputs 0(4)–20 mA / 0(1)–10 V; 3 analog outputs U, I, P; 3 alarm relays
Measurement32-bit processor, 1.5 million measurements/s, 15 bit
DisplayThyro-Touch 2.8 inch with data logger and SD card
Control supply90–265 V AC or 24 V DC
Dimensions 1PXfrom 150×320×232 mm, 6 kg (16–110 A) to 593×837×474 mm, 107 kg (5000 A)
CertificatesCE; UL 508: up to 500 V / 280 A, up to 690 V / 80 and 200 A

Replacement for

ROT-63, ROT-160, ROT-250E (including 700 V version), ROT-630, ROT-630M, ROT-800E, ROT-1400E, ROT-2600E (Thyro-PX 1PX version, single-phase, 16–5000 A; 500 V and 690 V)

selected by purpose and main parameters, please confirm with the manager

Replacement pages: РОТ-63, РОТ-160, РОТ-250Е, РОТ-630, РОТ-630М, РОТ-800Е, РОТ-1400Е, РОТ-2600Е

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Single-phase 1PX comes in two voltage classes. The 500 V type runs from 230 V −20 %…500 V +10 % and is built for 16, 37, 75, 110, 130, 170, 280, 350, 495, 650, 780, 1000, 1500, 2100, 2900 and 5000 A, the 690 V type from 500 V −20 % to 690 V +10 % for 80–2000 A. 2PX and 3PX serve three-phase loads, and above catalog currents the maker offers water-cooled stacks. A 32-bit processor takes 1.5 million measurements per second at 15-bit resolution, and power accuracy is ±1 %. Besides TAKT and VAR there is sequential voltage control VSC, which cuts distortion and reactive power, plus soft start and stop, with regulation by U, U², I, I² or P. Up to three analog setpoint inputs, three U, I, P actual-value outputs, three alarm relays and load circuit monitoring are on board. The 2.8-inch Thyro-Touch display with logger and SD card speeds up setup and fault analysis, built-in dASM lowers peak demand, and communication runs over PROFIBUS, PROFINET, EtherNet/IP, EtherCAT or Modbus TCP.

How to choose

The model follows from the load current, the 500 or 690 V class and the 1PX, 2PX or 3PX circuit. Housing size and weight grow steeply with current, so check them early when laying out the cabinet. For rectified current in electrolysis there is Thyro-PX DC for 1000–1800 A DC, and for typical heating up to 1500 A Thyro-A is enough.

Request a price and lead time

Thyro-PX — digital thyristor power controller, 1/2/3 phases, 16–5000 A, up to 1000 V. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What can replace a ROT-2600E regulator?

A single-phase Thyro-PX 1PX, whose range overlaps regulators from ROT-63 to ROT-2600E (Soviet-era single-phase thyristor voltage regulators). Selection by duty, current, load type and voltage is confirmed by a sales manager.

Which Thyro-PX replaces a 700 V ROT version?

The 690 V type, with a network from 500 V −20 % to 690 V +10 % and currents of 80–2000 A.

Does Thyro-PX work with molybdenum disilicide heaters?

Yes, the MOSI start mode is meant for heaters whose hot resistance is up to 20 times higher than the cold one.

What supply does the Thyro-PX control circuit need?

The control circuit has its own AC or 24 V DC supply, separate from the power section.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.