Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

VOLTAGE STABILIZERS

Three-phase stepped voltage stabilizers Volter 100 / 150 / 200 (105–210 kW)

Three-phase stepped stabilizers Volter 100, 150 and 200 with thyristor switching are rated 105, 165 and 210 kW at 160, 250 and 320 A. They feed large workshops, pumping stations, warehouses and shopping complexes. The cabinet enclosure stands on the floor and cooling is natural.

Models and power
Volter-100 — 105 kW, 160 A; Volter-150 — 165 kW, 250 A; Volter-200 — 210 kW, 320 A; Volter-100 U — 105 kW, 160 A, 7 steps
Dimensions (H×W×D)
1310×1900×250 mm (100); 1610×2300×300 mm (150, 200)
Weight
350 kg (100); 570 kg (150); 650 kg (200)
Accuracy
S — ±6.5 % (9 steps); PT/PTS — +1.5/−2.5 % (100, 150) and +2.5/−3.5 % (200), 16 steps

Technical specifications

Models and powerVolter-100 — 105 kW, 160 A; Volter-150 — 165 kW, 250 A; Volter-200 — 210 kW, 320 A; Volter-100 U — 105 kW, 160 A, 7 steps
Dimensions (H×W×D)1310×1900×250 mm (100); 1610×2300×300 mm (150, 200)
Weight350 kg (100); 570 kg (150); 650 kg (200)
AccuracyS — ±6.5 % (9 steps); PT/PTS — +1.5/−2.5 % (100, 150) and +2.5/−3.5 % (200), 16 steps
Typeelectronic thyristor (stepped regulation)
Efficiency98 %
Response time20 ms
Output voltage220 V per phase
Transit cut-off260 ± 5 V
Turn-on delay4.5–7.5 s
Coolingnatural
Protection degreeIP20
Operating conditions+1…+40 °C indoors, humidity 40–80 %
Frost-resistant treatmentto order

Analogues in the catalogue

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The Volter-100 U variant is built for 7 steps. Model 100 measures 1310×1900×250 mm and weighs 350 kg, while models 150 and 200 are 1610×2300×300 mm and 570 and 650 kg. Version S gives ±6.5 % on 9 steps, and versions PT and PTS on 16 steps give +1.5/−2.5 % for models 100 and 150 and +2.5/−3.5 % for model 200. Response time is 20 ms, efficiency 98 % and output 220 V per phase. The transit cut-off threshold is 260 ± 5 V and the turn-on delay 4.5–7.5 s. Protection acts against overload, short circuit, overheating and overvoltage. IP20 and the conditions of +1…+40 °C at 40–80 % humidity mean an indoor room. Frost-resistant treatment is made to order.

How to choose

The model is chosen by current, with 100 giving 105 kW at 160 A, 150 giving 165 kW at 250 A and 200 giving 210 kW at 320 A. Take PT or PTS for tighter stabilization and S for the simplest case. If stepless regulation is needed, there is the inverter Smart-100 at 105 kW and 160 A per phase, and for lower powers the three-phase Smart 10.5–81 kW (3×4 … 3×27). The European analogues in the catalogue cover 70–140 kVA and 100–2000 kVA. Supplied as the official representative in Ukraine.

Request a price and lead time

Three-phase stepped voltage stabilizers Volter 100 / 150 / 200 (105–210 kW), Volter. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What power and current do models 100, 150 and 200 have?

Model 100 is rated 105 kW and 160 A, model 150 165 kW and 250 A, and model 200 210 kW and 320 A.

How much do these stabilizers weigh?

Model 100 weighs 350 kg, model 150 weighs 570 kg and model 200 weighs 650 kg.

How many steps do the S, PT and PTS versions have?

S has 9 steps, PT and PTS have 16 steps, and the 100 U variant has 7 steps.

Does the stabilizer need maintenance?

Cooling is natural and the thyristor circuit has no moving parts, so no maintenance is needed.

Similar products

Voltage stabilizers

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.