Aquarius three-phase static voltage stabilizer 10–120 kVA
Country: · Model: Aquarius
Aquarius is a three-phase static IGBT stabilizer of 10–120 kVA. Regulation is per phase, accuracy ±0.5 %, permitted load asymmetry up to 100 %. An Aquarius plus version with an input breaker and a manual bypass is available.
- Power
- 10–120 kVA
- Regulation
- static, IGBT, per-phase
- Output voltage
- 220/230/240 V (phase-neutral), 380/400/415 V (line)
- Accuracy
- ±0.5 %
Technical specifications
| Power | 10–120 kVA |
|---|---|
| Regulation | static, IGBT, per-phase |
| Output voltage | 220/230/240 V (phase-neutral), 380/400/415 V (line) |
| Accuracy | ±0.5 % |
| Load asymmetry | up to 100 % |
| Overload | 150 % for 2 s |
Ukrainian replacement/analogue
- Three-phase inverter voltage stabilizers Volter Smart 10.5–81 kW (3×4 … 3×27)
- Three-phase inverter voltage stabilizer Volter Smart-100 (105 kW)
- Three-phase inverter voltage stabilizers Volter EtalonS 10.5–42 kW (3×4 … 3×14)
- Three-phase inverter voltage stabilizers Volter Prostor 21–42 kW (3×7 … 3×14)
- Three-phase inverter voltage stabilizers Volter Parus 21–42 kW (3×7 … 3×14)
- Three-phase inverter voltage stabilizers Volter PTTM 21–42 kW (3×7 … 3×14) with switching rack
- Three-phase stepped voltage stabilizers Volter 100 / 150 / 200 (105–210 kW)
- Three-phase stepped thyristor voltage stabilizers Hertz-PRO V3.0, 66–106 kW (3×100 … 3×160 A)
- Three-phase inverter voltage stabilizers 16.5–52.8 kW (Quant 3×5.5 … 3×18) with phase control unit
- Three-phase inverter voltage stabilizers 66–216 kW (Quant-66 … Quant-216) with power combiner
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
The static design has no moving parts, and the voltage of each phase is corrected separately by IGBT switches. For this reason single-phase consumers can load the line unevenly, since the stabilizer withstands asymmetry up to 100 % without going out of tolerance. The output voltage is chosen from 220, 230 or 240 V between phase and neutral, which in line terms gives 380, 400 or 415 V. The short-term overload is 150 % for 2 s. The plus version additionally has an input breaker and a manual bypass, which makes it possible to take the unit out of service without de-energizing the load.
How to choose
For small and medium sites compare the load power with the 10–120 kVA range and choose the rated output voltage. If input breaker protection and a manual bypass are needed, take the Aquarius plus. On a single-phase line up to 40 kVA the Gemini of 4–40 kVA is simpler, and from 80 kVA with double conversion and an overload of 120 % for 60 s the Odyssey of 80–4000 kVA works.
Request a price and lead time
Aquarius three-phase static voltage stabilizer 10–120 kVA. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What power range does the Aquarius cover?
10–120 kVA. For large sites of 80–4000 kVA there is the Odyssey.
Does the Aquarius withstand an unbalanced load?
Yes, load asymmetry up to 100 % is permitted, because each phase is regulated separately.
How does the Aquarius plus differ from the basic model?
The plus version has an input breaker and a manual bypass, which the basic one does not have.
What overload is permitted for the Aquarius?
150 % for 2 s. For prolonged starting modes it is better to take a reserve in rated power.
What is the voltage regulation accuracy of the Aquarius?
±0.5 % at an output voltage of 220, 230 or 240 V between phase and neutral, or 380, 400 or 415 V line.
Similar products
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.