Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

DC-DC CONVERTERS AND BATTERY CHARGERS

RCRFn rectifier-chargers 24–220 V DC

RCRFn rectifier-chargers form operational DC of 24, 48, 110 or 220 V DC and at the same time charge a stationary battery. The special version RCRFn 28V600A delivers 28 V at 600 A. The equipment is used in the power industry, industry, transport and petrochemical facilities.

Output voltage
24, 48, 110, 220 V DC; 28 V/600 A (RCRFn 28V600A)
Current (LC-R)
10–60 A, 1- or 3-phase input
Technology
thyristor or IGBT, input isolation transformer
Control
microprocessor; PLATINIUM 4.0: industrial PLC and 7″ touch panel

Technical specifications

Output voltage24, 48, 110, 220 V DC; 28 V/600 A (RCRFn 28V600A)
Current (LC-R)10–60 A, 1- or 3-phase input
Technologythyristor or IGBT, input isolation transformer
Controlmicroprocessor; PLATINIUM 4.0: industrial PLC and 7″ touch panel
BatteriesAGM, Pb, Ni-Cd

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The compact LC-R series is rated for 10–60 A and is fed from a single-phase or three-phase mains. The power section is made with thyristors or IGBTs, and an isolation transformer at the input galvanically separates the DC circuit from the mains. Such isolation is important for substation circuits, where DC busbars operate isolated from earth. Standard control is microprocessor-based; the PLATINIUM 4.0 version has an industrial PLC and a 7″ touch panel for setting and monitoring parameters. Charging characteristics are adjusted for AGM, flooded lead Pb and nickel-cadmium Ni-Cd batteries.

How to choose

The deciding parameters are the nominal battery voltage and the load current together with the charging current. For 24–220 V and a current up to 60 A the LC-R series is suitable, and for special 28 V supply there is RCRFn 28V600A. If the site is integrated into a process control system, choose PLATINIUM 4.0 with a PLC. For currents up to 1000 A the cabinet-type RDC is designed, and for modular N+1 redundancy the AUPUS system.

Request a price and lead time

RCRFn rectifier-chargers 24–220 V DC. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What output voltages does RCRFn have?

24, 48, 110 and 220 V DC, as well as a separate 28 V version at 600 A.

Which batteries does RCRFn work with?

With AGM, flooded lead Pb and nickel-cadmium Ni-Cd batteries; the charging mode is adjusted to the type.

What is included in the PLATINIUM 4.0 version?

An industrial PLC and a 7″ touch panel instead of the standard microprocessor control.

What is the current of the RCRFn LC-R series?

10–60 A when fed from a single-phase or three-phase mains.

Does RCRFn have galvanic isolation from the mains?

Yes, an isolation transformer is installed at the input regardless of whether the power section is thyristor or IGBT.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.