Horizon — three-phase diode and thyristor rectifier bridges, 60–2500 A, 24–690 V

Horizon three-phase rectifier bridges, diode or thyristor, deliver 60–2500 A DC at 24–690 V. They serve electroplating, electrolysis, electrochemical machining, DC heating and large drives.

Types
three-phase diode bridge; three-phase thyristor (controlled) bridge
Purpose
unidirectional AC to DC converter
Voltage
24–690 V
Rated current
60–2500 A

Technical specifications

Typesthree-phase diode bridge; three-phase thyristor (controlled) bridge
Purposeunidirectional AC to DC converter
Voltage24–690 V
Rated current60–2500 A
Semiconductor protectionRC networks, fuses with trip microswitch (relay output)
Auxiliary supply1 phase, 230 V AC, 50 Hz
Coolingforced air, heatsink with cooling tunnel
Designmodular aluminium frame, copper parts protected against oxidation, open module for panel mounting
Measurementbuilt-in current transformer optional
Maintenancefront phase replacement in ≤10 min, phase weight about 16 kg
ApprovalsCE, UKCA, EMC

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The diode bridge is uncontrolled, while the thyristor bridge regulates output voltage by phase angle control. Each semiconductor has an RC network and a fuse, the fuses sit inside the bridge, and their tripping goes to a relay contact. A current transformer for load measurement can be built in on request. The electronics are fully isolated from the power section and run on single-phase 230 V 50 Hz. Cooling is forced air through a tunnel formed by a specially shaped heatsink. The frame is built from aluminium modules, copper busbars are treated against oxidation, and the bridge is an open module for the cabinet backplate. Boards, fuses and thyristors are visible with the front door open, and the front panel shows the circuit and diagnostics. One technician removes a phase of about 16 kg from the front by undoing four screws, no lift truck needed, so replacement and downtime stay within 10 minutes. The bridges meet EMC requirements and carry CE and UKCA marking.

How to choose

A diode bridge gives unregulated rectified voltage and is simpler to maintain. The thyristor version sets output current and voltage smoothly and limits inrush current, so it suits electrolysis and plating with process regulation. Then size the bridge by output current and voltage within 60–2500 A and 24–690 V. For AC loads, such as heaters formerly run by ROT regulators, take REVO C rated 30–2100 A.

Request a price and lead time

Horizon — three-phase diode and thyristor rectifier bridges, 60–2500 A, 24–690 V. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How long does a phase replacement on a Horizon bridge take?

No more than 10 minutes, as one technician removes the phase of about 16 kg from the front by undoing four screws.

What is the difference between the diode and thyristor Horizon bridges?

The diode bridge gives unregulated rectified voltage, while the thyristor bridge regulates output current and voltage by phase angle control and limits start-up current.

How are the thyristors and diodes in Horizon bridges protected?

Each semiconductor has an RC network and a fuse with a trip microswitch reported via a relay contact.

What auxiliary supply does a Horizon bridge need?

Single-phase 230 V 50 Hz, with electronics fully isolated from the power section.

Can the load current of a Horizon bridge be measured?

Yes, a current transformer for load measurement can be built in on request.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.