PowerTitan 3.0 ST6900UX-4H — 20-ft BESS container, 6.9 MWh, with SiC PCS

PowerTitan 3.0 is a 20-ft BESS container holding 6,904 kWh of LFP cells with built-in silicon carbide (SiC) converters. AC power is 4 × 450 kVA at 690 V with THDi below 1%, so current harmonics put almost no stress on the substation transformer. It comes in DC and AC versions for grid and generation projects.

Capacity
6,904 kWh
Cell chemistry
LFP
DC voltage
1,101.6–1,489.2 V
AC power
4 × 450 kVA, 690 V, transformerless

Technical specifications

Capacity6,904 kWh
Cell chemistryLFP
DC voltage1,101.6–1,489.2 V
AC power4 × 450 kVA, 690 V, transformerless
THDi< 1%
Protection ratingIP55, corrosion resistance C4
Operating temperature−30 to +45 °C, liquid cooling
Dimensions / weight6,058 × 2,896 × 2,438 mm, 55 t
StandardsUL 9540A, IEC 62619, IEC 62933-5-2, IEC 62477-1, IEC 62443-4-2
Customs codes (for reference)
HS code8507.60
UKTZED code (Ukraine)8507600000
CN code (EU)85076000

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

The container ships pre-installed and already commissioned, so on site it goes onto the foundation and gets connected. Its converters support virtual inertia and grid voltage regulation, which helps a weak grid hold frequency and voltage. The design is transformerless with a 690 V output, so an external step-up transformer is needed to reach medium voltage. DC voltage is 1,101.6–1,489.2 V. Cooling is liquid, operating temperature −30 to +45 °C, and the enclosure is IP55 with C4 corrosion resistance. It measures 6,058 × 2,896 × 2,438 mm and weighs 55 t, which calls for a heavy tractor unit and a crane. The system complies with UL 9540A, IEC 62619, IEC 62933-5-2, IEC 62477-1 and IEC 62443-4-2, the last one covering control system cybersecurity.

How to choose

PowerTitan 3.0 is the pick when one site needs a lot of energy in the fewest containers. At 6,904 kWh it is denser than the PowerTitan 2.0 ST5015UX at 5,015 kWh in the same 6,058 × 2,896 × 2,438 mm footprint. If the project is built on a central PCS with a 4,000 kVA transformer, the ST2236UX battery container at 2,236 kWh paired with an SC4000UD-MV fits better. Commercial sites at 125 kW are served by the PowerStack 255CS cabinet.

Request a price and lead time

PowerTitan 3.0 ST6900UX-4H — 20-ft BESS container, 6.9 MWh, with SiC PCS. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the capacity of the PowerTitan 3.0 ST6900UX-4H?

6,904 kWh in a single 20-ft container.

What is the AC power of the ST6900UX-4H?

4 × 450 kVA at 690 V, transformerless.

How much does the PowerTitan 3.0 container weigh?

55 t at 6,058 × 2,896 × 2,438 mm.

Does the ST6900UX-4H need a transformer for grid connection?

The converters are transformerless with a 690 V output, so a medium-voltage connection needs an external step-up transformer.

What temperature range does PowerTitan 3.0 operate in?

−30 to +45 °C with liquid cooling, in an IP55 enclosure with C4 corrosion resistance.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.