FMC, FM, FGM — gas filters DN 15–300, 2 or 6 bar, filtration 10–50 µm
Country: · Model: FMC, FM, FGM
FMC, FM and FGM gas filters cover diameters DN 15–300 and pressures of 2 or 6 bar, with filtration of 10, 20 or 50 µm. They are installed at the start of a gas train or at the inlet before the pressure regulator, after the shut-off valve.
- FMC
- compact, Rp DN 15–25, 2 or 6 bar
- FM / FGM
- Rp DN 15–50, PN 16 flanges DN 25–50; FM — with wound cartridge, FGM — with flat central cartridge; 2 or 6 bar
- FM DN 65–300
- PN 16 flanges (ISO 7005 / EN 1092-1), ANSI 150 on request, 2 or 6 bar
- Filtration
- 10, 20 or 50 µm (DN 125–300 — 10 µm only)
Technical specifications
| FMC | compact, Rp DN 15–25, 2 or 6 bar |
|---|---|
| FM / FGM | Rp DN 15–50, PN 16 flanges DN 25–50; FM — with wound cartridge, FGM — with flat central cartridge; 2 or 6 bar |
| FM DN 65–300 | PN 16 flanges (ISO 7005 / EN 1092-1), ANSI 150 on request, 2 or 6 bar |
| Filtration | 10, 20 or 50 µm (DN 125–300 — 10 µm only) |
| Filter element | washable synthetic material, fully removable |
| Options | pressure and differential pressure test points, condensate drain plug/cock, clogging indicator (FGM, FM of large DN) |
| Ambient temperature | −40…+70 °C |
| Standards | EN 126, EN 13611; Regulation (EU) 2016/426; PED 2014/68/EU |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
The cartridge of washable synthetic material is fully removable for inspection, cleaning or replacement, and the body does not need to be removed from the pipeline. The filter retains dust and so protects burners, meters, boilers, regulators and solenoid valves. The maximum pressure of 2 or 6 bar (200 or 600 kPa) depends on the marking, and the ambient temperature can be from −40 to +70 °C. FMC has an Rp thread at DN 15, 20 and 25. FM and FGM are made with an Rp thread DN 15–50 and with PN 16 flanges from DN 25 (swivel) to DN 50. FM has a wound cartridge, FGM has a central flat-surface cartridge and a place for a differential pressure gauge. Large FM at DN 65, 80, 100, 125, 150, 200, 250 and 300 are intended for inlets and gas regulating stations, with PN 16 flanges per ISO 7005 and EN 1092-1, ANSI 150 on request. At DN 125–300 only 10 µm filtration is available. Standards are EN 126 and EN 13611 (mechanical strength group 2), Regulation (EU) 2016/426 and PED 2014/68/EU, with production approved under module D.
How to choose
The diameter is taken from the pipe, the filtration from the most sensitive device downstream, and for installations with long gaps between servicing, a clogging indicator and condensate drain are ordered. For fast emergency shut-off, SM/SMO are installed alongside, and ITG regulates the flow on modulating burners.
Request a price and lead time
FMC, FM, FGM — gas filters DN 15–300, 2 or 6 bar, filtration 10–50 µm. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What is the filtration of FM and FGM?
10, 20 or 50 µm. For DN 125–300 only 10 µm is produced.
What maximum pressure do the filters have?
2 or 6 bar (200 or 600 kPa) depending on the marking.
Does the filter need to be removed from the pipe to clean the cartridge?
No. The washable synthetic cartridge is fully removable without dismantling the body.
What flanges do the large FM filters have?
PN 16 per ISO 7005 and EN 1092-1, and ANSI 150 is made on request.
Similar products
GBC / GBS / GBS-H / LANCEFIREGBC, GBS, GBS-H, LANCEFIRE gas burners for industrial furnaces, 15–5000 kW
MPA 41xx V2.0MPA 41xx V2.0 and FLW/UV 4x flame sensors, burner control units per EN 298
Selectra M/MRSelectra electronic gas flame modulation systems: M/MR valves (3.4 kPa inlet), amplifiers, sensors, controllers
WGL30/1, WGL40/1WGL30–WGL40 compact dual-fuel gas/oil burners 70–550 kWREQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.