SR400/SR500/SR600 — two-stage gas pressure regulators (hi-lo), nominal inlet 3.4 kPa

SR400, SR500 and SR600 two-stage gas pressure regulators with a nominal inlet pressure of 3.4 kPa and a capacity of up to 28.3 m³/h. One device sets two outlet pressure levels, high and low flame, so a separate regulator and a second gas manifold for the burner are not needed.

Models
SR400, SR500, SR600
Connections
3/8"–1" NPT or ISO 7-1 thread
Function
pressure regulation + staged flame change (two outlet pressure setpoints)
Nominal inlet pressure
CSA: 1/2 psi (3.4 kPa); tested by the manufacturer up to 1 psi (6.9 kPa)

Technical specifications

ModelsSR400, SR500, SR600
Connections3/8"–1" NPT or ISO 7-1 thread
Functionpressure regulation + staged flame change (two outlet pressure setpoints)
Nominal inlet pressureCSA: 1/2 psi (3.4 kPa); tested by the manufacturer up to 1 psi (6.9 kPa)
Emergency limit2.5 psi (17.2 kPa)
Flowup to 1000 CFH (28.3 m³/h)
Bodyaluminium, vertical mounting only
Ambient temperature−40…+79 °C
CertificationANSI Z21.18/CSA 6.3 (except versions with the -2 suffix)

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The SR series combines pressure regulation and staged flame change (hi-lo) without an extra regulator or duplicate piping. The connection is threaded from 3/8 to 1 inch (NPT or ISO 7-1), the body is aluminium, and mounting is vertical only. The nominal inlet pressure under CSA is 1/2 psi (3.4 kPa), the manufacturer tests the regulators at 1 psi (6.9 kPa), and the emergency limit at the inlet is 2.5 psi (17.2 kPa). Capacity reaches 1000 cubic feet per hour (28.3 m³/h), and ambient temperature is from −40 to +79 °C. The regulators work on natural, manufactured and mixed gases, LPG and LPG-air mixtures. Certification to ANSI Z21.18/CSA 6.3 covers all versions except those with the -2 suffix. Typical applications are direct-fired air heaters with two-speed fans, outdoor heaters, and switching between LPG and natural gas. A nominal inlet of up to 5 kPa classes the device as low-pressure equipment.

How to choose

SR400, SR500 and SR600 are chosen by gas flow and connection; diagrams of minimum controllable flow and capacity are given in the manufacturer's catalogue. If the inlet pressure is above 3.4 kPa but does not exceed the tested 6.9 kPa, the manufacturer's instructions apply. For other tasks there are direct-acting regulators RV52–RV111 with an inlet up to 20 kPa and lever-type 325 with an inlet up to 100 kPa.

Request a price and lead time

SR400/SR500/SR600 — two-stage gas pressure regulators (hi-lo), nominal inlet 3.4 kPa. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What inlet pressure do SR regulators allow?

Nominal under CSA 3.4 kPa, manufacturer's tests up to 6.9 kPa, emergency limit 17.2 kPa.

What is the capacity of SR regulators?

Up to 1000 cubic feet per hour, that is 28.3 m³/h.

Can SR be mounted horizontally?

No, only vertical mounting is permitted; the body is aluminium.

What gases and temperatures does SR work with?

Natural, manufactured and mixed gases, LPG and its mixtures with air, at an ambient temperature from −40 to +79 °C.

Similar products

Burners and gas valves

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.