Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

INVERTERS

Proteus PCS-E — bidirectional energy storage inverter, 1500 V, up to 5.5 MVA

The Proteus PCS 4180E, 4360E, 4600E, 4910E and 5150E bidirectional inverters (PCS) convert battery DC to AC during discharge and the other way round during charging. AC power at 40 °C and 1500 V DC is from 4183 to 5153 kVA, up to 5477 kVA at 25 °C, and up to 5535 kVA at 1300 V DC. They are installed in utility-scale battery energy storage systems (BESS).

Models
Proteus PCS 4180E / 4360E / 4600E / 4910E / 5150E
AC power at 40 °C, 1500 V DC
4183 / 4365 / 4607 / 4910 / 5153 kVA
Power at 25 °C
up to 5477 kVA
DC voltage
up to 1500 V (min. 976–1202 V depending on model)

Technical specifications

ModelsProteus PCS 4180E / 4360E / 4600E / 4910E / 5150E
AC power at 40 °C, 1500 V DC4183 / 4365 / 4607 / 4910 / 5153 kVA
Power at 25 °Cup to 5477 kVA
DC voltageup to 1500 V (min. 976–1202 V depending on model)
Max. DC current2 × 2227 A
DC-side short-circuit withstand2 × 250 kA, 3 ms (two DC buses)
AC voltage690 / 720 / 760 / 810 / 850 V ±15 %
Current THD< 1 %
Max. efficiency98.57 %
Operating temperature−20…+60 °C
Functionsfour quadrants, grid forming, synthetic inertia, fast frequency response, black start

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Rated AC voltage is 690, 720, 760, 810 and 850 V (±15 %), and power is 4183, 4365, 4607, 4910 and 5153 kVA at 40 °C and 1500 V DC, respectively by model. The minimum DC voltage for grid operation is 976–1202 V depending on the model. Maximum efficiency is 98.57 %, standby consumption is below 200 W, and current harmonic distortion is below 1 %. Two independent power modules without galvanic isolation connect two separate batteries, which reduces short-circuit currents on the DC side, and short-circuit withstand is 2 × 250 kA for 3 ms. The design is independent of battery technology; lithium-ion, lead-acid or flow batteries can be used. Operation is four-quadrant, with active and reactive power support, operation in weak grids and microgrids with black start, synthetic inertia and grid forming. Cooling is CoolBrid, operating temperature is −20…+60 °C, and altitude up to 2000 m without derating. 50 MW of PCS-E inverters have been supplied to one customer.

How to choose

Choose the model by power and AC voltage. From the 4180E to the 5150E, power at 40 °C and 1500 V DC rises from 4183 to 5153 kVA, and AC voltage from 690 to 850 V. Two separate batteries on two DC buses reduce short-circuit currents and raise system availability. If you need an inverter for a PV plant without storage, see the Proteus PV 4100–4700 up to 4.7 MVA.

Request a price and lead time

Proteus PCS-E — bidirectional energy storage inverter, 1500 V, up to 5.5 MVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

Which models are in the Proteus PCS-E series?

Proteus PCS 4180E, 4360E, 4600E, 4910E and 5150E, with AC power at 40 °C from 4183 to 5153 kVA.

Which battery types does the inverter work with?

The design is independent of technology: lithium-ion, lead-acid, flow and others.

What is the maximum efficiency?

98.57 %, with standby consumption below 200 W.

Does the inverter support grid forming?

Yes: grid forming, synthetic inertia, fast frequency response and black start, in four quadrants.

What is the short-circuit withstand?

On the DC side 2 × 250 kA for 3 ms, because two separate batteries are connected to two buses.

Similar products

Inverters

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.