Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

INVERTERS

Sunny Central Storage UP / UP-XT / UP-S — central battery inverter (PCS) up to 5,000 kVA

The Sunny Central Storage central battery inverter acts as a PCS rated up to 3,960 kVA in the UP version, 4,600 kVA in UP-XT and 5,000 kVA in UP-S. It serves large energy storage systems with DC voltage up to 1,500 V, either alone or as part of a medium-voltage block.

Power
UP up to 3,960 kVA, UP-XT up to 4,600 kVA, UP-S up to 5,000 kVA (no derating at 35 °C)
DC voltage
up to 1,500 V
UP-S semiconductors
SiC MOSFET
UP-S functions
grid-forming, black start

Technical specifications

PowerUP up to 3,960 kVA, UP-XT up to 4,600 kVA, UP-S up to 5,000 kVA (no derating at 35 °C)
DC voltageup to 1,500 V
UP-S semiconductorsSiC MOSFET
UP-S functionsgrid-forming, black start
CoolingOptiCool
More from the manufacturer’s documentation
ModelsSCS 3450 / 3600 / 3800 / 3950 UP; SCS 3450 / 3600 / 3800 / 3950 UP-XT; SCS 2930 / 3060 / 4400 / 4600 UP-S
Operating DC voltage rangefrom 880–1,500 V to 1,003–1,500 V depending on model
Max. DC current4,750 A (UP, UP-XT, SCS 4400 / 4600 UP-S); 3,200 A (SCS 2930 / 3060 UP-S)
Max. DC short-circuit currentover 500 kA
AC power at 50 °C2,930–3,365 kVA (UP), 3,400–3,910 kVA (UP-XT), 2,640–4,140 kVA (UP-S)
Max. AC current (35 °C)3,320 A (UP); 3,850 A (UP-XT, SCS 4400 / 4600 UP-S); 2,566 A (SCS 2930 / 3060 UP-S)
Nominal AC voltage600 / 630 / 660 / 690 V depending on model
Grid frequency50 Hz (47–53 Hz) / 60 Hz (57–63 Hz)
Power factor1; adjustable 0.0 overexcited to 0.0 underexcited
Total harmonic distortion< 3% at nominal power
Max. efficiency98.8% (UP, UP-XT); 99.45% (UP-S)
Degree of protectionIP54 (electronics) / IP34 (air duct, connection area)
Dimensions (W × H × D)2,815 × 2,318 × 1,588 mm
Weight< 3,700 kg; < 3,400 kg (SCS 2930 / 3060 UP-S)
Self-consumption< 8,100 W (max.), < 370 W (standby)
Sound power level93 dB(A) (UP, UP-XT), 89–91 dB(A) (UP-S); Silencer Kit reduces by > 6 dB(A)
Operating temperature−25 °C to +60 °C (optional from −40 °C)
Storage temperature−40 °C to +70 °C
Relative humidity0–95% non-condensing; 95–100% up to 2 months per year
Installation altitudeup to 1,000 m (optional 2,000 m)
Fresh air consumption6,500 m³/h
InterfacesEthernet, Modbus Master, Modbus Slave; Modbus TCP / Ethernet (FO MM, Cat-5)
Grid functionsQ(U), P(f), FRT, active islanding detection, peak shaving, energy shifting
ProtectionDC load-break switch, AC circuit breaker, type I surge arresters, lightning protection level III (IEC 62305-1), insulation monitoring
Enclosure / roof colorRAL 9016 / RAL 7004
StandardsCE, IEC/EN 62109-1/-2, VDE-AR-N 4110/4120 (4130 for UP-S); EMC IEC 61000-6-2, EN 55011, FCC Part 15 Class A; DIN EN ISO 9001
Customs codes (for reference)
HS code8504.40
UKTZED code (Ukraine)8504408800 (>7.5 kVA)
CN code (EU)85044087

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

The UP-S delivers full power with no derating at 35 °C. Its power stage uses SiC MOSFETs, peak efficiency reaches 99.45% against 98.8% for the UP and UP-XT, and the firmware supports grid-forming operation and black start. All versions are cooled by OptiCool moving 6,500 m³/h of air, with IP54 electronics. Grid functions include Q(U), P(f), FRT ride-through, peak shaving and energy shifting. The battery connects through a DC load-break switch, and the cabinet has insulation monitoring and type I surge arresters. When shipped with a substation, a ready PCS block with transformer arrives on site. The unit weighs up to 3,700 kg at 2815 × 2318 × 1588 mm and sits on a prepared foundation.

How to choose

For arbitrage and peak shaving on a strong grid, the UP or UP-XT is enough. An island, microgrid or project that demands black start needs the UP-S with grid-forming and VDE-AR-N 4130. On a hot site size by the 50 °C rating, 3,400–3,910 kVA for the UP-XT and 2,640–4,140 kVA for the UP-S. The nominal AC voltage of 600, 630, 660 or 690 V is matched to the transformer winding. A smaller, modular BESS is easier to build on the Sunny Highpower Storage string inverter at 100–180 kVA.

Request a price and lead time

Sunny Central Storage UP / UP-XT / UP-S — central battery inverter (PCS) up to 5,000 kVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the rating of the Sunny Central Storage UP-S?

Up to 5,000 kVA with no derating at 35 °C, and up to 4,140 kVA at 50 °C.

Does the Sunny Central Storage support grid-forming?

Yes, the UP-S version supports grid-forming and black start, while neither is listed for the UP and UP-XT.

How do the UP and UP-XT versions of the Sunny Central Storage differ?

In power rating, the UP goes up to 3,960 kVA and the UP-XT up to 4,600 kVA. Maximum AC current at 35 °C is 3,320 and 3,850 A respectively.

What battery voltage does the Sunny Central Storage need?

The DC window runs from 880–1,500 V to 1,003–1,500 V depending on the model, with a maximum DC current of 4,750 A. The module count per battery rack is set to fit that window.

Similar products

Inverters

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.