Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

INVERTERS

50K-4T grid-tied string inverter 50 kW

A compact 50 kW inverter for a three-phase 400 V grid with an AC overload capability of 110 %, that is, with an output of up to 55 kVA. It is intended for commercial and industrial rooftop solar plants and for projects modernising old plants.

Rated power
50 kW (max. 55 kVA)
MPP trackers
4 (2 inputs each)
Max. PV power
75 kWp
DC voltage
max. 1100 V; MPPT 540–850 V

Technical specifications

Rated power50 kW (max. 55 kVA)
MPP trackers4 (2 inputs each)
Max. PV power75 kWp
DC voltagemax. 1100 V; MPPT 540–850 V
Grid3P/N/PE 230/400 V
Efficiencymax. 98.8 %, European 98.2 %
Protection ratingIP65, −30…+60 °C
Dimensions / weight480×585×220 mm, 37 kg
ProtectionDC SPD type I+II, AFCI (option)

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The four MPP trackers have two inputs each, so eight strings with a total peak power of up to 75 kWp are connected to the unit. The lower tracking limit is raised to 540 V, the upper is 850 V, and the absolute maximum DC voltage is 1100 V. The output connects to a 3P/N/PE 230/400 V grid. The highest efficiency is 98.8 %, the European efficiency 98.2 %. The 480×585×220 mm case is the same as for the 25K-3T and 33K-3T, and the weight is only a kilogram more, 37 kg. The operating temperature range is from −30 to +60 °C with an IP65 protection rating. A type I+II SPD is installed on the DC side, and AFCI arc-fault shutdown is available as an option.

How to choose

The deciding factors here are the 50 kW rating and the array limit of 75 kWp. When strings are short and in heat their voltage may fall below 540 V, the 25K-3T or 33K-3T, whose tracking starts from 480 V, are more appropriate. For a roof of 150 or 165 kWp it is simpler to install one 110K-10T or 125K-10T with ten trackers than several 50 kW units.

Request a price and lead time

50K-4T grid-tied string inverter 50 kW. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What does the 110 % AC overload capability in the 50K-4T inverter give?

At a rating of 50 kW the inverter can deliver up to 55 kVA to the grid. The margin in apparent power is needed when the grid operator requires reactive power generation without curtailing active power.

What is the minimum string voltage for tracker operation in the 50K-4T?

MPP tracking works from 540 to 850 V. The string is built so that in summer the operating voltage does not fall below 540 V, and in winter the open-circuit voltage does not exceed 1100 V.

Is the 50K-4T suitable for modernising an old solar plant?

Yes, the model is designed for modernisation projects too. A rating of 50 kW with an array of up to 75 kWp makes it possible to replace several older units of lower power with one.

Where can the 50K-4T be mounted?

The IP65 case withstands −30 to +60 °C, so the unit is installed outdoors on a roof or on a support structure. With a weight of 37 kg the wall or frame must be designed for such a load.

Similar products

Inverters

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.