WC / FC analog wattmeters, varmeters, power factor meters (cos φ) and frequency meters

The analog panel wattmeters, varmeters, power factor meters and frequency meters of the WC and FC series give a clear pointer indication of power, power factor and frequency. They are installed in generator, synchronizing and marine panels, as well as in substations and industrial switchgear. The housings range in size from 48×48 to 144×144 mm.

Wattmeters / varmeters
electronic (with a transducer) and induction; single- and three-phase, balanced and unbalanced networks
Power factor meters
induction and electronic; scale CAP 0.5–1–0.5 IND (90°) and 240°
Reed frequency meters
FC5V…FC2V: 48×48–144×144 mm; 7–21 reeds; 45–55 / 55–65 Hz; accuracy 0.5 %
Pointer frequency meters
FC5A…FC2A, 90° scale; accuracy 0.5 %; 100–440 V

Technical specifications

Wattmeters / varmeterselectronic (with a transducer) and induction; single- and three-phase, balanced and unbalanced networks
Power factor metersinduction and electronic; scale CAP 0.5–1–0.5 IND (90°) and 240°
Reed frequency metersFC5V…FC2V: 48×48–144×144 mm; 7–21 reeds; 45–55 / 55–65 Hz; accuracy 0.5 %
Pointer frequency metersFC5A…FC2A, 90° scale; accuracy 0.5 %; 100–440 V
Dual and differential frequency metersfor generator synchronization (FC3VI, FC2VI, FC3AII, FC3AD)
Voltage100√3, 110√3, 100, 110, 230, 400, 440 V; ±15 % Vn
Housings48×48, 72×72, 96×96, 144×144 mm
StandardsEN 60051, EN 61010, VDE 0410; DNV (FC3V)

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Electronic wattmeters with a built-in transducer show active power steadily in single-phase and three-phase, balanced and unbalanced networks, and induction ones are designed for long-term operation, as are varmeters for reactive power. WC series models, for example WC3V and WC5VrE, have different scales. Power factor meters measure the power factor with a CAP 0.5–1–0.5 IND (90°) or 240° scale. The reed frequency meters FC5V, FC4V, FC3V and FC2V (48×48, 72×72, 96×96 and 144×144 mm) have 7–21 reeds, ranges from 48.5–51.5 to 45–55 Hz (55–65 Hz for 60 Hz), a dual-scale 50/60 Hz version, an accuracy of 0.5 % and a consumption of 1.2–2.2 VA, and FC3V has a DNV certificate. The pointer-type FC5A–FC2A with a 90° scale have an accuracy of 0.5 % and a consumption of 10 mA. For comparing frequencies during synchronization there are the dual FC3VI, FC2VI, FC3AII and the differential FC3AD.

How to choose

The type of instrument is determined by the quantity. Active power is measured by wattmeters, reactive power by varmeters, and phase shift by power factor meters. For frequency take a reed FC_V if a clear scale is needed, or a pointer FC_A. For comparing two networks during synchronization, dual or differential frequency meters are required. Choose the cutout size, 48×48, 72×72, 96×96 or 144×144 mm, and the voltage to suit the panel.

Request a price and lead time

WC / FC analog wattmeters, varmeters, power factor meters (cos φ) and frequency meters. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What voltages do the FC frequency meters support?

100√3, 110√3, 100, 110, 230, 400 or 440 V with a tolerance of ±15 % Vn. The consumption of the reed types is 1.2–2.2 VA.

In what range do the reed frequency meters work?

From 48.5–51.5 to 45–55 Hz, 55–65 Hz for 60 Hz, 7–21 reeds, accuracy 0.5 %. A dual-scale 50/60 Hz version is available.

What are the protection rating and operating temperature?

IP52, IP54 or IP65 on request, operating temperature −25…+40 °C, test voltage 2 kV 50 Hz for 1 min.

Which standards and CE declarations apply to these instruments?

EN 60051, EN 61010, VDE 0410 and BS 89, with housings per IEC 61554. CE declarations are available for the WC and FC series, and FC3V has a DNV certificate.

Similar products

Test and measurement

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.