БПТ-658 — thermocouple signal converter with galvanic isolation
Country: Ukraine · Model: БПТ-658
input 1–100 mV · accuracy ±0.25 % · supply 18–30 V DC · isolation 2000 V
The БПТ-658 is a single-channel analogue signal conditioner. It accepts a signal from a type J, L, E, K, S, B or A-1 thermocouple and produces a standardised current or voltage output for indicators, controllers and data acquisition systems. The input thermo-EMF of 1–100 mV is converted linearly, without linearisation of the characteristic. A built-in circuit compensates for the temperature of the thermocouple cold junction. Input, output and power circuits are separated by galvanic isolation rated at no less than 2000 V, which eliminates stray currents and ground loops. Basic accuracy is ±0.25 % and measurement time is 0.01–0.5 s. The unit is powered from 18–30 V DC and draws 30 mA. Its 7 mm wide IP20 housing mounts on a DIN rail and operates from −40 to +70 °C. Typical applications include power generation, metallurgy and the chemical industry, as well as process automation and monitoring systems.
- Number of channels
- 1
- Thermocouple types
- J, L, E, K, S, B, A-1
- Input signal range
- 1–100 mV
- Output 0–5 mA
- Rн ≤ 2000 Ω
Technical specifications
| Number of channels | 1 |
|---|---|
| Thermocouple types | J, L, E, K, S, B, A-1 |
| Input signal range | 1–100 mV |
| Output 0–5 mA | Rн ≤ 2000 Ω |
| Output 0–20 mA | Rн ≤ 500 Ω |
| Output 4–20 mA | Rн ≤ 500 Ω |
| Output 0–10 V | Rн ≥ 2000 Ω |
| Conversion characteristic | linear, non-linearised |
| Cold-junction compensation | built-in |
| Accuracy | ±0.25 % |
| Measurement time | 0.01–0.5 s |
| Supply voltage | 18–30 V DC |
| Current consumption | 30 mA |
| Galvanic isolation voltage | 2000 V (input/output/supply) |
| Mounting | DIN rail DIN35x7,5 EN50022 |
| Wire cross-section | ≤ 2.5 mm², spring terminals |
| Protection rating | IP20 |
| Ambient temperature | −40…+70 °C |
| Dimensions | 94 × 7 × 64 mm |
| Weight | 0.1 kg |
| Standards | ДСТУ 2838-94, ДСТУ EN 60529, ДСТУ IEC 60654-1:2001, ДСТУ IEC 60654-3:2001, ДСТУ 2887-94, ДСТУ 3272: 2011, ДСТУ 2888-94, ДСТУ ГОСТ 2.610:2006 |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
When ordering, specify the thermocouple type (J, L, E, K, S, B, A-1) and the required temperature range (within 0–2000 °C depending on type). Choose the output to suit the load: 0–5 mA for Rн ≤ 2000 Ω, 0–20 or 4–20 mA for Rн ≤ 500 Ω, or 0–10 V for Rн ≥ 2000 Ω. For two channels, use the БПТ-122 version (76×26×115 mm, 0.2 kg).
Similar products
Request a price and lead time
БПТ-658 — thermocouple signal converter with galvanic isolation. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.