Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

БПВІ-1 — mutual inductance to standard signal converter unit

input 0–10 mH or −10…0…+10 mH · output 0–5 mA, 0–20 mA, 4–20 mA, 0–10 V · error ±0.25 % · supply 230 V AC / 24 V DC

The БПВІ-1 is a signal conditioning unit for mutual inductance sensors based on the differential transformer principle. It continuously and proportionally converts an input signal of 0–10 mH or −10…0…+10 mH into a standard current output of 0–5 mA, 0–20 mA or 4–20 mA, or into a 0–10 V voltage output. The basic reduced error does not exceed ±0.25 % and the measurement period is 0.01 s. The input, output and supply circuits are galvanically isolated, with an insulation strength of at least 500 V. The unit is powered from 230 V AC mains or a 24 V DC source. Its 96x100x110 mm IP30 housing mounts on a DIN rail and operates at ambient temperatures from −40 to +70 °C. Zero and span are set with potentiometers. Typical partners include pressure gauges, differential pressure gauges, vacuum gauges, compound gauges, low-pressure and draught gauges, and rotameters in pressure, level and flow monitoring systems on industrial sites.

Input signals
0 - 10 mH, -10 - 0 - +10 mH
Output signals
0 to 5 mA, 0 to 20 mA, 4 to 20 mA, 0 to 10 V
Supply voltage
230 V AC, 24 V DC
Power consumption
5 VA (AC), 120 mA (DC)

Technical specifications

Input signals0 - 10 mH, -10 - 0 - +10 mH
Output signals0 to 5 mA, 0 to 20 mA, 4 to 20 mA, 0 to 10 V
Supply voltage230 V AC, 24 V DC
Power consumption5 VA (AC), 120 mA (DC)
Basic reduced error limit± 0.25 %
Measurement period0.01 s
Galvanic isolationat least 500 V
MountingDIN rail (EN50022)
Housing dimensions96x100x110 mm
Weight0.5 kg
Degree of protectionIP30
Ambient temperature-40 °C to +70 °C
VersionsБПВІ-1 — base; БПВІ-10 — 2 discrete outputs, RS-485 (Modbus RTU), digital display
StandardsГОСТ 22261, ГОСТ 26828, ГОСТ 12971, ГОСТ 23170, ГОСТ 15150-69, ДСТУ ГОСТ 2.610

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

When ordering, choose the input range: 0–10 mH for unidirectional sensors or −10…0…+10 mH for bidirectional ones. The output can be 0–5 mA, 0–20 mA, 4–20 mA or 0–10 V, and the supply either 230 V AC or 24 V DC. If you need two discrete outputs, an RS-485 interface with Modbus RTU and a digital display, choose the БПВІ-10 version.

Similar products

Test and measurement

Request a price and lead time

БПВІ-1 — mutual inductance to standard signal converter unit. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.