The CNT-4 is a compact, microprocessor-based impulse counter with four independent channels. It accepts signals from mechanical, electronic, inductive and optical discrete sensors. Each of its 4 discrete inputs is processed separately. Readings are shown on an OLED display and retained in non-volatile memory. The unit switches its 4 discrete outputs when set points are reached or on command via RS-485 (Modbus RTU) or USB. Outputs can be transistor, relay or solid-state relay type. The counter registers pulses at up to 20 kHz with a minimum duration of 5 µs. A logic 1 corresponds to 3.3–30 V. Circuits have galvanic isolation of at least 500 V. The unit runs from 12–36 V DC or 100–242 V AC. Its 98 x 54 x 58 mm housing mounts on a DIN rail and operates from −40 °C to 70 °C. Typical tasks include counting products, length, weight, volume and distance. It is used in the food industry, in process automation systems and as part of SCADA systems.

Number of counters
4
Number of discrete inputs
4
Number of discrete outputs
4
Maximum pulse frequency
20 kHz

Technical specifications

Number of counters4
Number of discrete inputs4
Number of discrete outputs4
Maximum pulse frequency20 kHz
Minimum pulse duration5 µs
Maximum input current5 mA
Logic 0 voltage0–1 V
Logic 1 voltage3.3–30 V
Transistor output, max. voltage / current40 V / 100 mA
Solid-state relay output, max. voltage / current40 V / 500 mA
Relay output, max. voltage / current230 V AC / 5 A
Galvanic isolation voltageat least 500 V
DC supply voltage12 V to 36 V
AC supply voltage100 V to 242 V
Power consumption (AC)not more than 1.5 VA
Current consumption (DC)60 mA
InterfacesRS-485, USB
ProtocolModbus RTU
DisplayOLED display
MountingDIN rail
Dimensions98 x 54 x 58 mm
Mounting depth65 mm
Weight0.35 kg
Ingress protectionIP30
Operating temperature−40 °C to 70 °C
Mean time between failuresat least 100,000 hours
Mean time to repairnot more than 4 hours
Mean service lifeat least 10 years
StandardsДСТУ EN 60529:2014, ДСТУ IEC 60654-1:2001, ДСТУ IEC 60654-3:2001, ДСТУ EN 61326-1

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

Choose the output type by load. Transistor outputs are rated 40 V / 100 mA, solid-state relays 40 V / 500 mA, and electromechanical relays 230 V AC / 5 A. Select the supply version to match site power: 12–36 V DC or 100–242 V AC. Where sensors need powering, an optional built-in 24 V input supply is available.

Similar products

Test and measurement

Request a price and lead time

CNT-4 — 4-channel impulse counter. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.