DHC-96, DCB, DM45, CC / CV / CW — digital panel instruments and measuring transducers

DHC-96, DCB, DCP-96 and DM45 digital panel instruments and transducers of the CC, CV, CW/CY and CPF series show electrical quantities on the panel and pass them to automation. DHC-96 has a 96 × 48 mm format, and CC-A converts a 1 or 5 A AC current into a standard signal. They are used on substation panels, in telemechanics and SCADA.

DHC-96
panel 96×48 mm; AC or DC parameters (shunt), process signals; 2 relays, 2 digital inputs, 20 mA analogue output; RS-485 Modbus/RTU; IP54
DHC-96 CPM 1500
DC ±150…1500 V, shunt 50–600 mV; V, A, kW, kWh DC
DCB, DCP-96, DM45
digital indicators in various formats
CC-A
AC current transducer (1/5 A) → 4–20 mA / 0–10 V; accuracy 0.2 % of full scale; insulation 3 kV, impulse 4 kV

Technical specifications

DHC-96panel 96×48 mm; AC or DC parameters (shunt), process signals; 2 relays, 2 digital inputs, 20 mA analogue output; RS-485 Modbus/RTU; IP54
DHC-96 CPM 1500DC ±150…1500 V, shunt 50–600 mV; V, A, kW, kWh DC
DCB, DCP-96, DM45digital indicators in various formats
CC-AAC current transducer (1/5 A) → 4–20 mA / 0–10 V; accuracy 0.2 % of full scale; insulation 3 kV, impulse 4 kV
CV / CW / CY / CPFtransducers for voltage, power, cos φ, frequency
CC-A supply115/230/400 V AC (−15…+20 %), 2.5 VA

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

DHC-96 shows on the screen the measured electrical quantity or a proportional value of a process signal, depending on the model. Two relay outputs make regulation and control possible, and there are also 2 digital inputs, a 20 mA analogue output, RS-485 Modbus/RTU and protection degree IP54. For DC systems there is the DHC-96 CPM 1500 for ±150, 300, 600, 1000 and 1500 V DC with current through a 50–600 mV shunt; it shows voltage, current, power and energy. The CC-A Out2 transducer accepts 1 or 5 A AC within 0–150 % In, withstands 300 % In continuously and consumes 0.2 VA. The outputs are 0–20 / 4–20 mA or 0–5 / 0–10 V, with an accuracy of 0.2 % of the upper limit for the RMS value of a 50 Hz signal. The supply is 115/230/400 V AC (−15…+20 %), 40–90 Hz, 2.5 VA. The insulation withstands 3 kV 50 Hz for 1 min, and a 4 kV impulse (1.2/50 µs).

How to choose

The instrument type depends on what exactly you measure. Output the current from a current transformer through CC-A, and voltage, power, cos φ and frequency through CV, CW/CY, CPF. For DC networks up to 1500 V take DHC-96 CPM 1500. If you need a network analyser with harmonics up to the 31st, look at CVM-C10 / C11.

Request a price and lead time

DHC-96, DCB, DM45, CC / CV / CW — digital panel instruments and measuring transducers. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the format of DHC-96 panel instruments?

The format is 96 × 48 mm. There are 2 relays, 2 digital inputs, RS-485 Modbus/RTU and IP54 protection.

What DC voltages does DHC-96 CPM 1500 measure?

Networks of ±150, 300, 600, 1000 and 1500 V DC, with current through a 50–600 mV shunt.

What output signals does the CC-A transducer have?

0–20 / 4–20 mA or 0–5 / 0–10 V, accuracy 0.2 % of the upper limit. Input 1 or 5 A AC.

What supply does CC-A need?

115/230/400 V AC with a tolerance of −15…+20 %, frequency 40–90 Hz, consumption 2.5 VA.

Similar products

Test and measurement

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.