ЭУ5000 — relay protection testing set
Country: Ukraine · Model: ЭУ5000
AC 54–380 V / 2–67.5 A · DC 110–240 V / 0.06–4.5 A · timer 0.1–9.9 s · supply 220 or 380 V
The ЭУ5000 is a testing set for commissioning and checking simple relay protection devices and automation elements such as relays, contacts and starters. It comprises two units: the ФР5000 regulation unit and the ФМ5000 load unit. The set runs from a 220 or 380 V mains supply and produces adjustable quantities at its output terminals to simulate network conditions. The AC output covers 54 to 380 V at currents from 2 to 67.5 A. The smoothed rectified DC output provides 110 to 240 V at 0.06 to 4.5 A. The load can be disconnected automatically in two ways: by the output relay contacts of the protection under test, or by a built-in timer adjustable from 0.1 to 9.9 s. Operate and reset times are measured with the built-in stopwatch or an external millisecond meter. The protection under test may also be powered from an external DC battery. The set is used on site at power plants and industrial enterprises, and in laboratories.
- Supply voltage
- 220 or 380 V
- AC output voltage
- 54–380 V
- AC output current
- 2–67.5 A
- AC output adjustment
- smooth-stepped
Technical specifications
| Supply voltage | 220 or 380 V |
|---|---|
| AC output voltage | 54–380 V |
| AC output current | 2–67.5 A |
| AC output adjustment | smooth-stepped |
| DC output (smoothed rectified): voltage | 110–240 V |
| DC output (smoothed rectified): current | 0.06–4.5 A |
| Non-adjustable DC output | 210 V / 1.00 A; 220 V / 0.65 A |
| DC output (unsmoothed rectified) | up to 4.5 A, smooth adjustment |
| Built-in timer setting range | 0.1–9.9 s |
| Automatic load disconnection | by output relay contacts of protection under test or by timer |
| Operate/reset time measurement | built-in stopwatch or external millisecond meter |
| Supply of protection under test | DC from external battery |
| Composition | ФР5000 regulation unit, ФМ5000 load unit |
| Dimensions of each unit | max. 490×210×520 mm |
| ФР5000 unit weight | max. 27.0 kg |
| ФМ5000 unit weight | max. 30.0 kg |
| Scope of supply (additional) | bag, cables К1, К2, К4, К5, К7, fuses 3.15 A, 10 A, 15 A |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
Choose the output mode to suit the device under test. AC current relays are tested from the high-current output of up to 67.5 A. Voltage relays are tested from the AC voltage output of up to 380 V. For DC apparatus, use the smoothed output of 110–240 V (up to 4.5 A). Where smoothly adjustable DC current is needed, use the unsmoothed output of up to 4.5 A. The 220 or 380 V supply arrangement is selected according to the available mains.
Similar products
Request a price and lead time
ЭУ5000 — relay protection testing set. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.