Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

ЭУ5000 — relay protection testing set

AC 54–380 V / 2–67.5 A · DC 110–240 V / 0.06–4.5 A · timer 0.1–9.9 s · supply 220 or 380 V

The ЭУ5000 is a testing set for commissioning and checking simple relay protection devices and automation elements such as relays, contacts and starters. It comprises two units: the ФР5000 regulation unit and the ФМ5000 load unit. The set runs from a 220 or 380 V mains supply and produces adjustable quantities at its output terminals to simulate network conditions. The AC output covers 54 to 380 V at currents from 2 to 67.5 A. The smoothed rectified DC output provides 110 to 240 V at 0.06 to 4.5 A. The load can be disconnected automatically in two ways: by the output relay contacts of the protection under test, or by a built-in timer adjustable from 0.1 to 9.9 s. Operate and reset times are measured with the built-in stopwatch or an external millisecond meter. The protection under test may also be powered from an external DC battery. The set is used on site at power plants and industrial enterprises, and in laboratories.

Supply voltage
220 or 380 V
AC output voltage
54–380 V
AC output current
2–67.5 A
AC output adjustment
smooth-stepped

Technical specifications

Supply voltage220 or 380 V
AC output voltage54–380 V
AC output current2–67.5 A
AC output adjustmentsmooth-stepped
DC output (smoothed rectified): voltage110–240 V
DC output (smoothed rectified): current0.06–4.5 A
Non-adjustable DC output210 V / 1.00 A; 220 V / 0.65 A
DC output (unsmoothed rectified)up to 4.5 A, smooth adjustment
Built-in timer setting range0.1–9.9 s
Automatic load disconnectionby output relay contacts of protection under test or by timer
Operate/reset time measurementbuilt-in stopwatch or external millisecond meter
Supply of protection under testDC from external battery
CompositionФР5000 regulation unit, ФМ5000 load unit
Dimensions of each unitmax. 490×210×520 mm
ФР5000 unit weightmax. 27.0 kg
ФМ5000 unit weightmax. 30.0 kg
Scope of supply (additional)bag, cables К1, К2, К4, К5, К7, fuses 3.15 A, 10 A, 15 A

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

Choose the output mode to suit the device under test. AC current relays are tested from the high-current output of up to 67.5 A. Voltage relays are tested from the AC voltage output of up to 380 V. For DC apparatus, use the smoothed output of 110–240 V (up to 4.5 A). Where smoothly adjustable DC current is needed, use the unsmoothed output of up to 4.5 A. The 220 or 380 V supply arrangement is selected according to the available mains.

Similar products

Test and measurement

Request a price and lead time

ЭУ5000 — relay protection testing set. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.