ЭУ5001 — relay protection testing unit
Country: Ukraine · Model: ЭУ5001
220 or 380 V supply · AC current up to 67.5 A · phase shift 0–360° · timer 0.1–9.9 s
The ЭУ5001 is a portable unit for commissioning and testing simple and complex relay protection schemes and automation elements, such as relays, contacts and starters. Testing is carried out directly where the protection is installed. The set comprises three blocks: the ФР5000 regulating block, the ФМ5000 loading block and the ФП5000 add-on block. It is powered from a 220 or 380 V mains supply. At its output terminals the unit delivers adjustable AC voltages of 54–380 V and currents of 2–35 A. A high-current mode provides up to 67.5 A. A smoothed rectified DC output covers 110–240 V at 0.06–4.5 A. A symmetrical three-phase voltage of 97–113 V is also available. The phase angle can be adjusted from 0 to 360°. A built-in 0.1–9.9 s timer simulates a fault condition and its recurrence. The unit reproduces single-, two- and three-phase short circuits. A built-in stopwatch measures the operating and reset times of the device under test. It is used at power plants, industrial enterprises and laboratories.
- Supply voltage
- 220 or 380 V
- AC output voltage
- 54–380 V
- AC output current
- 2–35 A
- High-current AC output voltage
- 112–250 V
Technical specifications
| Supply voltage | 220 or 380 V |
|---|---|
| AC output voltage | 54–380 V |
| AC output current | 2–35 A |
| High-current AC output voltage | 112–250 V |
| High-current AC output current | 12–67.5 A |
| AC output regulation | smooth-stepped |
| DC output voltage (smoothed rectified) | 110–240 V |
| DC output current (smoothed rectified) | 0.06–4.5 A |
| Unregulated DC outputs | 210 V / 1.00 A; 220 V / 0.65 A |
| DC current (unsmoothed rectified) | 4.5 A, smooth regulation |
| Symmetrical three-phase voltage | 97–113 V, 2 A (unregulated) |
| Phase-to-neutral voltage adjustment | 0 to (97–113) V |
| Phase shift adjustment range | 0–360° |
| Timer range (fault simulation) | 0.1–9.9 s |
| Short-circuit simulation | single-, two- and three-phase |
| Operate/reset time measurement | built-in stopwatch or external millisecond timer |
| Composition | ФР5000 regulating block, ФМ5000 loading block, ФП5000 add-on block |
| Dimensions of each block, max. | 490×210×520 mm |
| ФР5000 block weight, max. | 27.0 kg |
| ФМ5000 block weight, max. | 30.0 kg |
| ФП5000 block weight, max. | 32.5 kg |
| Scope of supply | bag, cables К1–К8, lugs, clamps, fuses 3.15 A, 10 A, 15 A, documentation |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Similar products
Request a price and lead time
ЭУ5001 — relay protection testing unit. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.