Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

R2M / RIC2VI / RMC2 / RSQ / RUFC2 / RVI / RSN protection and monitoring relays for generators and LV networks

The relays R2M, R2MC, RIC2VI, RMC2, RSQ, RUFC2, RVI and RSN from the marine series protect generating sets and monitor the state of three-phase low-voltage networks. They are installed on diesel generator sets, in marine and onshore generating stations, in substations and in 0.4 kV switchgear.

R2M / R2MC
active power / current relay for a three-phase network; current input x/5 A, voltage input direct; setpoint on the front panel
RIC2VI
reverse power relay (anti-motoring) for generators in parallel operation; setpoint 2–15 % Pn
RMC2
electronic overcurrent relay per phase for three-phase generators; time delay indication
RSQ
phase sequence relay with an enabling contact 250 V, 8 A; 3 LEDs

Technical specifications

R2M / R2MCactive power / current relay for a three-phase network; current input x/5 A, voltage input direct; setpoint on the front panel
RIC2VIreverse power relay (anti-motoring) for generators in parallel operation; setpoint 2–15 % Pn
RMC2electronic overcurrent relay per phase for three-phase generators; time delay indication
RSQphase sequence relay with an enabling contact 250 V, 8 A; 3 LEDs
RUFC2min./max. voltage and frequency relay, three- and single-phase networks
RVImonitoring of substation measuring circuits: current and voltage unbalance, over- and undervoltage; 2 alarm relays
RSNmarine protection relay for generating sets; RS485, USB (setup without auxiliary supply), up to 2 digital inputs
StandardsEN 60051, EN 61010; CE

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Most models are made in panel housings with light indication of operation and setpoints on the front panel, which are covered by a screw or a plug. R2M and R2MC measure active power or current in a three-phase network; the current input is x/5 A and the voltage input is direct. RIC2VI limits reverse power between two parallel generators with a setpoint of 2–15 % Pn at 50–60 Hz, and the kW scale corresponds to Un × In × √3 × cos φ. RMC2 monitors the current of each generator phase and shows the time delay countdown. RSQ shows the phase sequence with three LEDs (red L1-L3-L2, green L1-L2-L3, OK on operation) and gives an enabling contact of 250 V, 8 A, with a consumption of 1.2 VA. RUFC2 watches the minimum and maximum voltage and frequency. RVI detects current and voltage unbalance, overvoltage and undervoltage, and a current fault switches on one alarm relay and a voltage fault the other. RSN connects to a central post over RS485, setpoints are set with potentiometers or over USB without auxiliary supply, and up to two digital inputs are available.

How to choose

To protect against a generator switching to motoring mode take RIC2VI, for overcurrent per phase RMC2, and for measuring current or power with a threshold R2M or R2MC. The correctness of the phase connection is checked by RSQ, and voltage and frequency deviations by RUFC2. Monitoring of measuring circuits in substations with two alarm relays is done by RVI, and remote supervision of a generator with operation logs by RSN.

Request a price and lead time

R2M / RIC2VI / RMC2 / RSQ / RUFC2 / RVI / RSN protection and monitoring relays for generators and LV networks. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the setpoint of the RIC2VI reverse power relay?

2–15 % Pn at a frequency of 50–60 Hz. The relay works between two AC generators operating in parallel.

What contact and consumption does RSQ have?

An enabling contact of 250 V, 8 A and a consumption of 1.2 VA. The correct sequence is shown by the green LED, the reverse one by the red LED.

How can RSN be set up without auxiliary supply?

Through the USB port. Setpoints can also be set with potentiometers on the front panel, and data and logs are transmitted over RS485.

Which standards and CE declarations apply to these relays?

EN 60051 and EN 61010. CE declarations are available for R2M, RIC2VI, RMC2, RUFC2 and RSN.

Similar products

Test and measurement

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.