Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

SC / RSS / RSC2 synchroscopes, digital synchronizing relays and generator synchronizing columns

The synchroscopes SC_V, the digital relays RSS1 and RSS3, and the synchro-check relay RSC2 are intended for parallel connection of AC generators with each other or with the network. The same marine series includes a ready-made synchronizing column with a voltmeter, a frequency meter and a synchroscope.

SC_V synchroscopes
phase synchronism of two networks or of a network and a generator; single- and three-phase; external resistor box
SC_VL lamp synchroscope
lamp indication
RSS1 / RSS3
digital synchronizing relay, 96×96 mm; input 110/230/400/440 V ±20 %; 45–65 Hz; phase difference ±180°; accuracy U 0.5 %, f 0.1 %, φ 1 %
RSC2
synchro-check relay for two generators: phase difference 5–40° el., delay 0.2–2.5 s, output contact for the breaker

Technical specifications

SC_V synchroscopesphase synchronism of two networks or of a network and a generator; single- and three-phase; external resistor box
SC_VL lamp synchroscopelamp indication
RSS1 / RSS3digital synchronizing relay, 96×96 mm; input 110/230/400/440 V ±20 %; 45–65 Hz; phase difference ±180°; accuracy U 0.5 %, f 0.1 %, φ 1 %
RSC2synchro-check relay for two generators: phase difference 5–40° el., delay 0.2–2.5 s, output contact for the breaker
Synchronizing columndual/differential voltmeter + dual/differential frequency meter + synchroscope; vertical (180° rotation) or horizontal
StandardsEN 60051, EN 61010; DNV (marine series)

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The SC_V synchroscopes check the equality of frequency and phase of two networks, single-phase or three-phase, or of a network and a generator, and are supplied with an external resistor box; SC_VL is a simple lamp version. RSS1 and RSS3 in a 96×96 mm housing show the phase and amplitude of two voltages and carry out the synchronizing maneuver. The input is 110, 230, 400 or 440 V ±20 % (RSS1 two-wire for 110 or 230 V, RSS3 three-wire for 110–440 V), the frequency 45–65 Hz, the phase difference ±180°, the voltage difference tolerance ±100 %, and the accuracy 0.5 % for voltage, 0.1 % for frequency and 1 % for phase and voltage difference. RSC2 compares the voltage, phase and frequency of two generators. The permissible phase difference is set within 5–40 electrical degrees, the minimum hold time is 0.2–2.5 s, and the phase accuracy is ±2.5 %. When both conditions are met, the output relay closes the synchronizing breaker. The synchronizing column is vertical with a swivel bracket for 180° rotation, or horizontal.

How to choose

For simple visual monitoring take SC_V or the lamp SC_VL. When numerical values of voltage, frequency and phase and an automatic maneuver are needed, choose RSS1 for a two-wire 110 or 230 V input or RSS3 for 110–440 V. An automatic command to the breaker based on the phase tolerance and the delay is given by RSC2. For a complete parallel-connection post, order the synchronizing column.

Request a price and lead time

SC / RSS / RSC2 synchroscopes, digital synchronizing relays and generator synchronizing columns. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the accuracy of RSS1 and RSS3?

0.5 % for voltage, 0.1 % for frequency and 1 % for phase and voltage difference. The frequency range is 45–65 Hz and the phase difference ±180°.

What setpoints does the RSC2 synchro-check relay have?

A permissible phase difference of 5–40 electrical degrees and a minimum time of 0.2–2.5 s. The phase accuracy is ±2.5 %.

What does the synchronizing column consist of?

A dual or differential voltmeter, the same kind of frequency meter, and a synchroscope. The design is vertical with 180° rotation, or horizontal.

Which standards do these instruments comply with?

EN 60051 and EN 61010, and the marine series has DNV. CE declarations are available for SC3V and RSS3.

Similar products

Test and measurement

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.