Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

Output circuit protection unit type BZ-2RPA

The output circuit protection unit BZ-2RPA monitors insulation resistance in a 36 V, 50 Hz network. In continuous monitoring mode it trips at 3 ± 0.5 kΩ, and in preventive monitoring mode at 4.2 ± 0.5 kΩ. It is supplied with 36 V, 50 Hz and has a 36 V output for the load.

Terminal no.
Purpose
1,2
Not used
3
Insulation monitoring voltage output, connected to earth.
4,5
Optotriac output for connecting the signal lamp Leakage 36V

Technical specifications

Terminal no.Purpose
1,2Not used
3Insulation monitoring voltage output, connected to earth.
4,5Optotriac output for connecting the signal lamp Leakage 36V
6,7Load relay input, also the power supply.
8,936V output for connecting the load.
10Terminal for checking that insulation measurement works.

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The unit is supplied with 36 V, 50 Hz within a permitted range of 85–115 % and protects a network of the same voltage. It monitors insulation in two ways. In continuous monitoring mode the trip resistance is 3 ± 0.5 kΩ, and in preventive monitoring mode it is 4.2 ± 0.5 kΩ. Terminals 1 and 2 are not used, and terminal 3 is the insulation monitoring voltage output connected to earth. Terminals 4 and 5 give an optotriac signal to the lamp labelled Leakage 36V. Terminals 6,7 are the load relay input, which also powers the unit, and terminals 8,9 give the 36 V output for the load. Terminal 10 is for checking that insulation measurement works.

How to choose

The unit is meant for 36 V, 50 Hz networks, so check the network voltage first. Continuous monitoring trips at the lower resistance, 3 ± 0.5 kΩ, and preventive monitoring at 4.2 ± 0.5 kΩ, so the choice depends on whether an early warning is needed. For intrinsically safe power supply look at the BPI-RPA unit.

Request a price and lead time

Output circuit protection unit type BZ-2RPA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

At what insulation resistance does the BZ-2RPA trip?

In continuous monitoring mode at 3 ± 0.5 kΩ, and in preventive monitoring mode at 4.2 ± 0.5 kΩ.

What voltage is the unit meant for?

It is supplied from 36 V, 50 Hz within 85–115 % and protects a 36 V, 50 Hz network.

What is connected to terminals 4 and 5?

The signal lamp labelled Leakage 36V, which the unit switches through an optotriac.

What is terminal 10 for?

For checking that insulation measurement works.

Where is the load connected?

To terminals 8,9, which give the 36 V output. Terminals 6,7 are the load relay input, which also powers the unit.

Similar products

Test and measurement

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.