Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

ІПМ-103 — three-phase network parameter indicator

1…400 V AC (direct connection) · 0.05–5.0 A (direct connection) · 45–65 Hz · 90–264 V AC supply

The ІПМ-103 is a panel indicator for monitoring the parameters of a three-phase electrical network: voltage, current, frequency, power and power factor. The measured signals are digitised by a built-in ADC and processed by a microcontroller. Readings appear on an OLED display, and the unit is configured from the front-panel keypad or from a PC. With direct connection it measures 1…400 V AC and 0.05–5.0 A. With external transformers the ranges extend to 4000×10^3 V and 50.0×10^3 A. Network frequency is monitored within 45–65 Hz. The input circuits have galvanic isolation of at least 2500 V. An RS-485 port with Modbus RTU and a USB port pass data to higher-level systems. The indicator runs from a 90–264 V AC supply, consumes no more than 2.0 W and mounts on a DIN rail. It operates from -40 to +70 °C. Typical applications include power engineering, metallurgy, and the chemical and food industries, where it supports electricity distribution monitoring, energy-efficiency projects and process automation systems.

Network type
three-phase
Supply voltage
90…264 V AC
Supply frequency
50 Hz
Power consumption
≤ 2.0 W

Technical specifications

Network typethree-phase
Supply voltage90…264 V AC
Supply frequency50 Hz
Power consumption≤ 2.0 W
Voltage measurement (direct)1…400 V AC
Voltage measurement (via transformer)1×10^-3…4000×10^3 V AC
Frequency range45–65 Hz
Current measurement (direct)0.05–5.0 A
Current measurement (via transformer)0.05×10^-3…50.0×10^3 A
Maximum voltage (1 s)800.0 V
Maximum current (1 s)10.0 A
Measurement error0.25–1.0 %
Input circuit galvanic isolationat least 2500 V
Galvanic isolation (insulation)at least 500 V
DisplayOLED display with keypad
InterfacesRS-485, USB
ProtocolModbus RTU
MountingDIN rail (DIN35x7,5 EN50022)
Degree of protectionIP20
Ambient temperature-40 °C to +70 °C
Dimensions (HxWxD)98x72x57 mm
Weightmax. 0.3 kg
VersionsІПМ-103-Т0 (internal current transformers), ІПМ-103-Т1 (external current transformers)

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

The ІПМ-103-Т0 version has built-in current transformers and is intended for direct connection of current circuits within 0.05–5.0 A. The ІПМ-103-Т1 version works with external current transformers. Choose it for installations with high currents, where the range extends to 50.0×10^3 A depending on the transformer ratio.

Similar products

Test and measurement

Request a price and lead time

ІПМ-103 — three-phase network parameter indicator. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.