ІПМ-113-2 — three-phase network parameter indicator-transducer
Country: Ukraine · Model: ІПМ-113-2
~1–400 V (direct connection) · 0.05–5.0 A (direct connection) · U, I error ±0.25 % · 45–65 Hz
The ІПМ-113-2 is a DIN-rail panel instrument for monitoring a three-phase network. It measures voltage, current, frequency, power and power factor, and shows the results on an OLED display with a keypad. Voltages up to ~400 V and currents from 0.05 to 5.0 A are connected directly, while higher values are measured through external transformers. Measurement error is ±0.25 % for voltage and current, ±0.5 % for power and ±0.15 % for frequency. Readings are updated every 1.0 s. Data are transmitted over RS-485 (Modbus RTU), and the unit is configured from a PC via USB. The instrument has two discrete outputs (an NPN transistor and a normally open relay) and one analogue output with ranges of 0–5 mA, 0–20 mA, 4–20 mA or 0–10 V. Galvanic isolation is rated at no less than 2500 V, and power consumption does not exceed 2.0 VA. Typical applications are power distribution monitoring and energy-efficiency projects at industrial sites.
- Voltage measurement (direct connection)
- ~ (1...400 V), 45–65 Hz
- Voltage measurement via external transformer
- ~ (1×10^-3...4000×10^3 V), 45–65 Hz
- Voltage resolution
- 1.0 V (on display)
- Voltage measurement error
- ± 0.25 %
Technical specifications
| Voltage measurement (direct connection) | ~ (1...400 V), 45–65 Hz |
|---|---|
| Voltage measurement via external transformer | ~ (1×10^-3...4000×10^3 V), 45–65 Hz |
| Voltage resolution | 1.0 V (on display) |
| Voltage measurement error | ± 0.25 % |
| Maximum permissible voltage | 800.0 V |
| Current measurement (direct connection) | 0.05 to 5.0 A |
| Current measurement via external transformer | (0.05х10^-3 ... 50.0х10^3) A |
| Current resolution | 0.01 (on display); 0.001 (via interface) |
| Current measurement error | ± 0.25 % |
| Maximum permissible current | 10.0 A |
| Measurement update period | 1.0 s |
| Power calculation time | 1.0 s |
| Power measurement error | ± 0.5 % |
| Power factor range | 0.0 to 1.0 |
| Power factor error | ± 1.0 % |
| Frequency range | 45.0 to 65.0 Hz |
| Frequency measurement error | ± 0.15 % |
| Galvanic isolation voltage | not less than 2500 V |
| Number of discrete outputs | 2 |
| Discrete output types | NPN transistor: up to 40 V, 100 mA; normally open relay: up to 230 V, 5 A |
| Number of analogue outputs | 1 |
| Analogue output ranges | 0–5 mA / R ≤ 2000 Ω; 0–20 mA / R ≤ 500 Ω; 4–20 mA / R ≤ 500 Ω; 0–10 V / R ≤ 2 kΩ |
| Interfaces | RS-485, USB |
| Protocol | Modbus RTU |
| Display | OLED display with keypad |
| Supply voltage | 230 V AC |
| Power consumption | ≤ 2.0 VA (AC) |
| Mounting | DIN rail |
| Degree of protection | IP20 |
| Ambient temperature | -40 °C to +70 °C |
| Dimensions | 98х100х57 mm |
| Weight | not more than 0.3 kg |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
The ІПМ-113 series differs in its output set. The ІПМ-113-2 has 2 discrete outputs (an NPN transistor and a relay) and 1 analogue output. The ІПМ-113-1 provides 3 discrete outputs and 1 analogue output in the same 98х100х57 mm housing. The ІПМ-113-3 has no discrete or analogue outputs and comes in a narrower 98х72х57 mm housing. It suits applications that need only indication and interface data transfer.
Similar products
Request a price and lead time
ІПМ-113-2 — three-phase network parameter indicator-transducer. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.