ІПМ-113-3 — three-phase network parameter indicator-transducer
Country: Ukraine · Model: ІПМ-113-3
1…400 V (direct connection) · 0.05–5.0 A (direct connection) · 45–65 Hz · ±0.25 % (voltage, current)
The ІПМ-113-3 is an indicator-transducer for monitoring the parameters of three-phase AC networks. It measures voltage, current, frequency, power and power factor, and it determines instantaneous, average and accumulated values. Voltages up to 400 V and currents from 0.05 to 5.0 A can be connected directly. With external transformers, the range extends to 4000×10^3 V for voltage and 50.0×10^3 A for current. Network frequency is measured from 45 to 65 Hz. Accuracy is ±0.25 % for voltage and current, ±0.5 % for power, ±1.0 % for cosφ and ±0.15 % for frequency. The measurements are converted into three unified analogue output signals. The unit also provides three discrete outputs and RS-485 (Modbus RTU) and USB interfaces. Configuration is carried out via an OLED display with keypad, and the unit mounts on a DIN rail. Typical uses include electricity distribution monitoring and energy-efficiency projects.
- Measured quantities
- voltage, current, frequency, power, cosφ
- Phases
- three-phase
- Voltage range (direct)
- ~1…400 V
- Voltage range (via transformer)
- ~1×10^-3…4000×10^3 V
Technical specifications
| Measured quantities | voltage, current, frequency, power, cosφ |
|---|---|
| Phases | three-phase |
| Voltage range (direct) | ~1…400 V |
| Voltage range (via transformer) | ~1×10^-3…4000×10^3 V |
| Current range (direct) | 0.05…5.0 A |
| Current range (via transformer) | 0.05×10^-3…50.0×10^3 A |
| Frequency range | 45.0…65.0 Hz |
| Accuracy (voltage/current) | ±0.25 % |
| Accuracy (power) | ±0.5 % |
| Accuracy (cosφ) | ±1.0 % |
| Accuracy (frequency) | ±0.15 % |
| Supply voltage | 230 V AC |
| Power consumption | ≤ 2.0 VA |
| Analogue outputs | 3 (0–5 mA, 0–20 mA, 4–20 mA, 0–10 V) |
| Analogue output load | up to 2000 Ω |
| Discrete outputs | 3 (NPN transistor or relay) |
| Discrete output voltage | up to 230 V |
| Discrete output current | up to 5.0 A |
| Interfaces | RS-485, USB |
| Protocol | Modbus RTU |
| Galvanic isolation voltage | 500…2500 V |
| Display | OLED display with keypad |
| Settings memory | EEPROM |
| Mounting | DIN rail |
| Degree of protection | IP20 |
| Operating temperature | -40 °C to +70 °C |
| Dimensions | 98×100×57 mm |
| Weight | max. 0.3 kg |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
The ІПМ-113-3 has 3 analogue and 3 discrete outputs. If fewer outputs are sufficient, choose the ІПМ-113-1 (1 analogue, 2 discrete) or the ІПМ-113-2 (3 analogue, 2 discrete). Discrete outputs are available as NPN transistor or relay types. The analogue output can be selected from 0–5 mA, 0–20 mA, 4–20 mA or 0–10 V. Current transformers may be internal or external. The unit can be powered from an external 230 V AC supply or from the measured network.
Similar products
Request a price and lead time
ІПМ-113-3 — three-phase network parameter indicator-transducer. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.