accuracy class 0.2 % · 0.1–5 A · RS-485 / Modbus RTU · -40 to +70 °C
The ІПМ-3Н is a microprocessor-based indicator-transducer for single-phase AC networks. It measures RMS current either directly or via a current transformer and shows the reading on a seven-segment display. The measured value is converted into a standard analogue signal of 0–5 mA, 0–20 mA, 4–20 mA or 0–10 V. A discrete output (NPN transistor or relay) is provided for alarms and control. An RS-485 interface with Modbus RTU passes data to SCADA systems. The accuracy class is 0.2 % and the measurement period is 0.1 s. The unit tolerates a twofold overload for up to 5 s. All circuits are galvanically isolated at no less than 1500 V. The operating temperature range is -40 to +70 °C. The device replaces analogue panel ammeters in process control systems for power generation, metallurgy, and the chemical and food industries.
- Measured quantity
- RMS single-phase AC current
- Measuring range
- 0.1÷1 A, 0.25÷2.5 A, 0.5÷5 A, from current transformer
- Accuracy class
- 0.2 %
- Measurement period
- 0.1 s
Technical specifications
| Measured quantity | RMS single-phase AC current |
|---|---|
| Measuring range | 0.1÷1 A, 0.25÷2.5 A, 0.5÷5 A, from current transformer |
| Accuracy class | 0.2 % |
| Measurement period | 0.1 s |
| Overload | 2×, for up to 5 s |
| Analogue output | 0–5 mA / R ≤ 2000 Ω; 0–20 mA / R ≤ 500 Ω; 4–20 mA / R ≤ 500 Ω; 0–10 V / R ≤ 2 kΩ |
| Discrete output | NPN transistor: up to 40 V, 100 mA; changeover relay: up to 230 V, 8 A; NO relay: up to 230 V, 5 A |
| Interface | RS-485 |
| Protocol | Modbus RTU |
| Display | seven-segment |
| Supply voltage AC | 230 V |
| Supply voltage DC | 24 V |
| Power consumption (AC) | ≤ 4.0 VA |
| Current consumption (DC) | max. 110 mA |
| Galvanic isolation voltage | min. 1500 V |
| Mounting | panel, DIN rail |
| Dimensions | 48х96х106 mm (panel), 98х54х57 mm (DIN) |
| Weight | max. 0.25 kg (panel), max. 0.15 kg (DIN) |
| Ingress protection | IP30 (panel), IP20 (DIN) |
| Operating temperature | -40 °C to +70 °C |
| Standards | ДСТУ IEC 60381-1, ДСТУ IEC 60654-1:2001, ДСТУ IEC 60654-3:2001, ДСТУ EN 60529:2014, ДСТУ EN 61326-1 |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
Select the measuring range: 0.1÷1 A, 0.25÷2.5 A, 0.5÷5 A, or operation from a current transformer. The panel-mount version (48х96х106 mm, IP30) suits front panels, while the DIN rail version (98х54х57 mm, IP20) suits enclosures. Also specify the analogue output (mA or 0–10 V), the discrete output (NPN transistor or relay), the supply (230 V AC or 24 V DC) and whether RS-485 is required.
Similar products
Request a price and lead time
ІПМ-3Н — single-phase AC current indicator-transducer. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.