ІТМ-11 — single-channel digital process indicator

accuracy ≤ 0.2 % · 18–36 V DC supply · RS-485, Modbus RTU · IP30

The ІТМ-11 is a microprocessor-based single-channel indicator for monitoring process variables such as temperature, pressure, humidity, level and flow. It accepts standard current and voltage signals (0–5 mA, 0–20 mA, 4–20 mA, 0–10 V, 0–75 mV, 0–200 mV, 0–2 V), Pt100 resistance thermometers and thermocouples of several types. Readings appear on a four-digit seven-segment LED display with 8 mm digits, supplemented by a 31-segment analogue bar. Accuracy is within 0.2 % and measurement time is up to 0.1 s. Two discrete outputs handle alarms or control, an optional analogue output retransmits the signal, and an RS-485 interface with Modbus RTU links the unit to automation systems. Input, outputs and interface are galvanically isolated. The unit runs on 18–36 V DC, is panel-mounted and operates from -40 to +70 °С. Typical sectors are energy, metallurgy, and the chemical and food industries. This model has been discontinued; the ІТМ-311 is its replacement. Discontinued. Current replacement: ІТМ-311.

Device type
Single-channel process indicator
Input signals (current, voltage)
0–5 mA, 0–20 mA, 4–20 mA, 0–10 V, 0–75 mV, 0–200 mV, 0–2 V
Input signals (temperature)
Pt100; thermocouples type K, L, J, S, B, E, A-1
Temperature measuring range
0…2500 °С

Technical specifications

Device typeSingle-channel process indicator
Input signals (current, voltage)0–5 mA, 0–20 mA, 4–20 mA, 0–10 V, 0–75 mV, 0–200 mV, 0–2 V
Input signals (temperature)Pt100; thermocouples type K, L, J, S, B, E, A-1
Temperature measuring range0…2500 °С
Accuracy≤ 0.2 %
Measurement timeup to 0.1 s
Galvanic isolation voltage≥ 500 V (input), ≥ 1500 V (outputs/interface)
Analogue output (optional)0–5 mA / R ≤ 2000 Ω, 0–20 mA / R ≤ 500 Ω, 4–20 mA / R ≤ 500 Ω
Number of discrete outputs2
Discrete output typesNPN transistor (≤ 40 V, 100 mA), electromechanical relay (≤ 230 V, 8 A), solid-state relay (≤ 60 V, 1 A)
InterfaceRS-485
ProtocolModbus RTU
Digital display4-digit 7-segment LED, 8 mm height
Analogue bar31 segments, horizontal front panel
Supply voltage18–36 V DC
Current consumption≤ 200 mA
Mountingpanel, cut-out 92x45 mm
Dimensions48x96x170 mm
Weight≤ 0.35 kg
Degree of protectionIP30
Operating temperature-40…+70 °С
StandardsDSTU IEC 60381-1, DSTU 2858-94, DSTU 2837-94, DSTU IEC 60654-1:2001
Statusdiscontinued, current replacement: ІТМ-311

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

When ordering, specify the input type: current, voltage, Pt100 or the required thermocouple. Then choose the discrete outputs: NPN transistor (≤ 40 V, 100 mA) for logic inputs, electromechanical relay (≤ 230 V, 8 A) for load switching, or solid-state relay (≤ 60 V, 1 A) for frequent switching. A 0–5, 0–20 or 4–20 mA analogue output is available as an option.

Similar products

Test and measurement

Request a price and lead time

ІТМ-11 — single-channel digital process indicator. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.