ІТМ-22 — two-channel universal microprocessor process indicator

2 analogue inputs · error ≤ 0.5 % · 4 discrete outputs · RS-485, Modbus RTU

The ІТМ-22 is a two-channel universal microprocessor indicator for measuring and displaying process variables such as temperature, pressure, humidity, level and flow. It handles signals from two independent analogue inputs. These include standard current signals of 0-5 mA, 0-20 mA and 4-20 mA, and voltage signals of 0-10 V, 0-75 mV, 0-200 mV and 0-2 V. It also accepts resistance thermometers and TXA (K) and TXK (L) thermocouples. Built-in processing provides digital filtering, linearisation and scaling. Measurement error is ≤ 0.5 % and measurement time is ≤ 0.1 s. Input galvanic isolation is rated at ≥ 500 V. Readings appear on a 4-digit 7-segment LED display with a vertical bar graph. Four discrete outputs and an RS-485 interface running Modbus RTU support alarm functions and integration into automation systems. The unit is panel-mounted with IP30 protection. Typical applications include energy, metallurgy, and the chemical and food industries. This model has been discontinued and is replaced by the ІТМ-322. Discontinued. Current replacement: ІТМ-322.

Device type
process indicator
Channels
2
Analogue inputs
2
Input signals
0-5 mA, 0-20 mA, 4-20 mA, 0-10 V, 0-75 mV, 0-200 mV, 0-2 V, TSM 50M, TSM 100M, TSM gr.23, TSP 50P, TSP 100P, TSP gr.21, TXA (K), TXK (L)

Technical specifications

Device typeprocess indicator
Channels2
Analogue inputs2
Input signals0-5 mA, 0-20 mA, 4-20 mA, 0-10 V, 0-75 mV, 0-200 mV, 0-2 V, TSM 50M, TSM 100M, TSM gr.23, TSP 50P, TSP 100P, TSP gr.21, TXA (K), TXK (L)
Temperature measuring range0 to 1300 °C
Measurement error≤ 0.5 %
Measurement time≤ 0.1 s
Input galvanic isolation≥ 500 V
Discrete outputs4
Discrete output typesNPN transistor (≤ 40 V, 100 mA), relay (≤ 230 V, 8 A), solid-state relay (≤ 60 V, 1 A)
InterfaceRS-485
ProtocolModbus RTU
Display4-digit 7-segment LED, vertical bar graph
AC supply~100 V to ~242 V, 6 VA
DC supply18 V to 36 V DC, 250 mA
Mountingpanel, 96x96 mm cutout
Dimensions96х96х190 mm
Weight≤ 0.35 kg
Degree of protectionIP30
Operating temperature-40 °C to +70 °C
StandardsDSTU IEC 60381-1, DSTU IEC 60381-2, DSTU 2858-94, DSTU 2837-94, ГОСТ 22261, ГОСТ 14254-96
VersionsІТМ-20 — without front-panel bar graph
Statusdiscontinued, current replacement: ІТМ-322

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

The ІТМ-22 has a vertical bar graph on the front panel. The ІТМ-20 version omits it. Choose the discrete output type to suit the load: NPN transistor (≤ 40 V, 100 mA), relay (≤ 230 V, 8 A) or solid-state relay (≤ 60 V, 1 A). Select the supply version to match the site supply: AC ~100 to ~242 V or DC 18 to 36 V.

Similar products

Test and measurement

Request a price and lead time

ІТМ-22 — two-channel universal microprocessor process indicator. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.