К507 — apparatus for verification of instrument current and voltage transformers
Country: Ukraine · Model: К507
verifies CTs and VTs of classes 0.05–10 · secondary current 0.5–6 A · secondary voltage 50–240 V · frequency 50 Hz
The К507 is a laboratory apparatus for verifying instrument current and voltage transformers by the differential-zero method. The transformer under test is compared with a reference transformer, and the difference signal between them is balanced. This yields the ratio (current or voltage) error and the phase-angle error. The apparatus handles transformers of accuracy classes 0.05, 0.1, 0.2, 0.5, 1, 3 and 10. It covers rated secondary currents of 1, 2, 2.5 and 5 A and rated secondary voltages of 100, 150 and 200 V at 50 Hz. Error measuring limits are 0.1, 0.3, 1, 3 and 10 %. It also measures the active and reactive components of impedance and admittance in the secondary circuits. It can serve as a rectangular-coordinate AC potentiometer as well. The built-in ammeter-voltmeter has an error of ±1.5 %, and the null indicator is supplied from (220 ± 22) V mains. Typical users are calibration and electrical laboratories, metrology departments of industrial plants and power utilities.
- Purpose
- verification of instrument current and voltage transformers
- Measuring method
- differential-zero
- Accuracy classes of transformers under test
- 0.05; 0.1; 0.2; 0.5; 1; 3; 10
- Rated secondary currents
- 1; 2; 2.5; 5 A
Technical specifications
| Purpose | verification of instrument current and voltage transformers |
|---|---|
| Measuring method | differential-zero |
| Accuracy classes of transformers under test | 0.05; 0.1; 0.2; 0.5; 1; 3; 10 |
| Rated secondary currents | 1; 2; 2.5; 5 A |
| Rated secondary voltages | 100; 150; 200 V |
| Operating secondary current range | 0.5–6 A |
| Operating secondary voltage range | 50–240 V |
| Frequency | 50 Hz |
| Ratio error measuring limits | ±0.1; ±0.3; ±1; ±3; ±10 % |
| Phase-angle error measuring limits | from −3.5…+6.5 to −350…+650 min |
| Active resistance component limits | 0.3; 1; 3; 10; 30; 100 Ω |
| Reactive resistance component limits | 0.6; 2; 6; 20; 60; 200 Ω |
| Active and inductive conductance limits | 3·10⁻⁴–300·10⁻⁴ S |
| Capacitive conductance limits | 6·10⁻⁴–600·10⁻⁴ S |
| AC potentiometer mode limits | up to 5 mV (5 A); up to 2.5 mV (2.5 A); up to 2 mV (2 A); up to 1 mV (1 A); up to 3 mV (200 V); up to 1.5 mV (100 V) |
| In-phase and quadrature component error | within ±2 % of full scale |
| Burden on reference current transformer | max 0.8; 0.6; 0.25 Ω at 1; 2–2.5; 5 A (cosφ = 0.8–1) |
| Burden on current transformer under test | max 0.01 Ω (cosφ = 1) |
| Burden on reference voltage transformer | max 7.5 VA (100 V); 10.0 VA (150 V); 15.0 VA (200 V) |
| Ammeter-voltmeter error | ±1.5 % of the working-range full scale |
| Null indicator supply | (220 ± 22) V, (50 ± 1) Hz |
| Power consumption | max 10 VA |
| Overall dimensions | 615 × 440 × 240 mm (handles extended: 710 × 480 × 240 mm) |
| Weight | max 24 kg |
Specifications are taken from the manufacturer’s technical documentation. Updated .