К535 — calibration device for current and voltage instrument transformers

CTs of class 0.02 and lower · VTs of class 0.05 and lower · 40–1000 Hz · secondary current 0.5–5 A

The К535 is designed to calibrate current transformers of accuracy class 0.02 and lower and voltage transformers of accuracy class 0.05 and lower. It determines the error components: the ratio error (current error for CTs, voltage error for VTs) and the phase-angle error. It also measures the active and reactive components of the burden in the secondary circuit of the transformer under test. Current transformers are tested by an absolute method using the И562 comparator, so no reference transformer is needed. The device handles VTs with secondary voltages of 100:3, 100:√3, 100, 200:√3, 150 and 200 V, and CTs with secondary currents of 0.5, 1, 2, 2.5 and 5 A. Error measuring ranges are ±0.2 %, ±2 % and ±20 %, with phase-angle error measured up to ±200′. The working frequency range is 40–1000 Hz. The set consists of two benchtop units: the Ф5304 measuring unit and the И562 comparator. Power comes from a (220 ± 22) V, (50 ± 0.5) Hz mains supply, and consumption does not exceed 50 V·A. The device is used in metrology and calibration laboratories for high-precision verification of current and voltage transformers.

Current transformers under test
accuracy class 0.02 and lower
Voltage transformers under test
accuracy class 0.05 and lower
VT rated secondary voltage
100:3; 100:√3; 100; 200:√3; 150; 200 V
CT rated secondary current
0.5; 1; 2; 2.5; 5 A

Technical specifications

Current transformers under testaccuracy class 0.02 and lower
Voltage transformers under testaccuracy class 0.05 and lower
VT rated secondary voltage100:3; 100:√3; 100; 200:√3; 150; 200 V
CT rated secondary current0.5; 1; 2; 2.5; 5 A
CT error measurement methodabsolute (no reference transformer)
Comparator rated ampere-turns100; 200; 300
Ratio (voltage/current) error ranges±0.2 %; ±2 %; ±20 %
Phase-angle error ranges±20′; ±200′
Reference frequency range (filter off)45–100 Hz
Working frequency range (filter off)40–1000 Hz
Burden measuring ranges (active/reactive)1, 10, 100 W (var)
Relative secondary voltage (current) ranges15 and 150 % of rated
Fiducial error of relative voltage (current) measurement±1.5 % (Ф5304 display); ±2.5 % (comparator analogue meter)
Comparator intrinsic absolute errorratio ±0.005 %; phase angle ±0.3′
Supply voltage(220 ± 22) V AC
Supply frequency(50 ± 0.5) Hz
Power consumptionmax. 50 V·A
CompositionФ5304 measuring unit, И562 comparator (benchtop)
Ф5304 measuring unit dimensions330x150x350 mm
Ф5304 measuring unit weightmax. 8.5 kg
И562 comparator dimensions450x300x470 mm
И562 comparator weightmax. 26.5 kg

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

Select the measuring range according to the expected error of the transformer under test. Range 0.2 (±0.2 %, ±20′) suits high-accuracy CTs and VTs, while ranges 2 and 20 cover less accurate units. Set the comparator ampere-turn rating (100, 200 or 300) to match the CT's primary and secondary currents. At 300 ampere-turns, only a 5 A secondary current is available.

Similar products

Test and measurement

Request a price and lead time

К535 — calibration device for current and voltage instrument transformers. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.