Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

SBT supervision system for the low-voltage side of transformer substations (SBT-TDM, SBT4V-5C, SBT-VTN, SBT-CDS, SBT-D)

SBT is a set of instruments for supervising the low-voltage side of transformer substations, connected to the output of the 0.4 kV power transformer and to the outgoing lines. It includes the SBT-TDM and SBT4V-5C analyzers, the SBT-VTN neutral monitor, the SBT-CDS concentrator and the SBT-D display. Data on the network state and faults goes to the dispatch center of the network company.

SBT-TDM
three-phase analyzer-digitizer for the output of a 0.4 kV power transformer; supply 24 V DC, input 1 A; dual RJ45 for daisy-chain connection
SBT4V-5C
digital LV analyzer: 3 voltages, 3 currents; 50–60 Hz; insulation 2 kV/1 min; Ethernet Modbus TCP, RS485 Modbus RTU; DIN rail
SBT-VTN
neutral-to-earth voltage monitoring 2–150 V, error <1 %, supply 24 V DC, 0.3 W, RJ45
SBT-CDS
data concentrator for SBT-TDM and SBT-VTN over RS485, transmission to the control center

Technical specifications

SBT-TDMthree-phase analyzer-digitizer for the output of a 0.4 kV power transformer; supply 24 V DC, input 1 A; dual RJ45 for daisy-chain connection
SBT4V-5Cdigital LV analyzer: 3 voltages, 3 currents; 50–60 Hz; insulation 2 kV/1 min; Ethernet Modbus TCP, RS485 Modbus RTU; DIN rail
SBT-VTNneutral-to-earth voltage monitoring 2–150 V, error <1 %, supply 24 V DC, 0.3 W, RJ45
SBT-CDSdata concentrator for SBT-TDM and SBT-VTN over RS485, transmission to the control center
SBT-DHMI display: table of 2×8 cells of 16 characters, 4 capacitive keys, RS485 Modbus
StandardsUNE-EN 61010-1, UNE-EN 61010-2-30, UNE-EN 60255-26, UNE-EN 61000-6-2/-6-4

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

SBT-TDM digitizes the parameters of a three-phase network: voltage, current, frequency, power, power factor, energy and harmonics. The supply is 24 V DC and the rated input is 1 A for low-power current transformers, and two RJ45 connectors link the modules in a chain, carrying power and data over one cable. SBT4V-5C collects three phase voltages relative to neutral and three main currents, works at 50–60 Hz, has 2 kV insulation for 1 min, Ethernet (Modbus TCP) and RS485 (Modbus RTU), and is mounted on a DIN rail. SBT-VTN watches the neutral-to-earth potential difference in the 2–150 V range with an error below 1 % and detects a broken neutral or leakage currents; its supply is 24 V DC and its consumption 0.3 W. SBT-CDS collects the data of SBT-TDM and SBT-VTN over RS485 and passes it to the control center. SBT-D is an HMI display with a table of 2 columns by 8 rows (up to 16 characters per cell), a header of up to 32 characters and 4 capacitive keys, controlled over RS485 Modbus.

How to choose

Start with what needs to be monitored. For the output of the power transformer take SBT-TDM, for individual outgoing lines with three voltages and currents SBT4V-5C, and for checking the neutral earthing SBT-VTN. SBT-CDS collects the data of several modules, and SBT-D provides local indication. For panel network analysis without a substation chain, look at AHM1, AHM3 or SAM3000.

Request a price and lead time

SBT supervision system for the low-voltage side of transformer substations (SBT-TDM, SBT4V-5C, SBT-VTN, SBT-CDS, SBT-D). We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What supply do the SBT modules have?

SBT-TDM and SBT-VTN are powered from 24 V DC, and SBT-VTN consumes 0.3 W. Two RJ45 connectors make it possible to pass power and data over one cable.

In what range does SBT-VTN monitor the neutral?

The neutral-to-earth potential difference of 2–150 V with an error below 1 %. This detects a break or deterioration of the neutral earthing and leakage currents.

What interfaces does SBT4V-5C have?

Ethernet (Modbus TCP) and RS485 (Modbus RTU), DIN-rail mounting, 2 kV insulation for 1 min, frequency 50–60 Hz.

Which standards does the SBT system comply with?

UNE-EN 61010-1, UNE-EN 61010-2-30, UNE-EN 60255-26 and UNE-EN 61000-6-2/-6-4. CE declarations are available for SBT-TDM, SBT-CDS and SBT-VTN.

Similar products

Test and measurement

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.