Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

ПНС-1 — DC voltage and current to standard analogue signal converter

conversion error 0.25 % · input from 0…75 mV to 0…500 V, 0…20 mA · output 4…20 mA, 0…20 mA, 0…5 mA, 0…10 V · supply 24 V DC / 230 V AC

The ПНС-1 is a measuring transducer that linearly converts a DC voltage or current signal into a standard analogue DC current or voltage signal. Accepted inputs range from millivolt-level shunt signals (0…75 mV) up to 0…500 V, plus current signals of 0…5 mA, 0…20 mA and 4…20 mA. The output is provided in the standard ranges 0(-5)…5 mA, 0(-20)…20 mA, 4…20 mA or 0(-10)…10 V. The input, output and supply circuits are galvanically isolated, with an insulation test voltage of 2000 V and an insulation resistance of at least 40 MΩ. The conversion error is 0.25 % and the conversion time does not exceed 6 s. The unit is powered from 24 V DC or 230 V AC, mounts on a DIN rail, is rated IP30 and operates from -40 to +70 °C. Typical applications include electrical network monitoring, telemechanics, automation of power facilities, and the metallurgical and chemical industries.

Voltage input signals
0 (-75)…75 mV (with shunt), R = 250 kΩ; 0 (-10)…10 V, R = 130 kΩ; 0 (-15)…15 V, R = 200 kΩ; 0 (-60)…60 V, R = 267 kΩ; 0 (-100)…100 V, R = 200 kΩ; 0 (-150)…150 V, R = 667 kΩ; 0 (-250)…250 V, R = 667 kΩ; 0 (-500)…500 V, R = 1.3 MΩ
Current input signals
0 (-5)…5 mA, R = 15 Ω; 0 (-20)…20 mA, R = 3.75 Ω; 4…20 mA, R = 3.75 Ω
Output signal
0(-5)…5 mA, 0(-20)…20 mA, 4…20 mA, 0(-10)…10 V
Supply voltage
24 V DC, 230 V AC

Technical specifications

Voltage input signals0 (-75)…75 mV (with shunt), R = 250 kΩ; 0 (-10)…10 V, R = 130 kΩ; 0 (-15)…15 V, R = 200 kΩ; 0 (-60)…60 V, R = 267 kΩ; 0 (-100)…100 V, R = 200 kΩ; 0 (-150)…150 V, R = 667 kΩ; 0 (-250)…250 V, R = 667 kΩ; 0 (-500)…500 V, R = 1.3 MΩ
Current input signals0 (-5)…5 mA, R = 15 Ω; 0 (-20)…20 mA, R = 3.75 Ω; 4…20 mA, R = 3.75 Ω
Output signal0(-5)…5 mA, 0(-20)…20 mA, 4…20 mA, 0(-10)…10 V
Supply voltage24 V DC, 230 V AC
Power consumptionDC: max. 120 mA; AC: ≤ 5.0 VA
Conversion error0.25 %
Conversion timemax. 6 s
Galvanic isolationbetween input, output and supply circuits
Insulation withstand voltage2000 V
Insulation resistancemin. 40 MΩ
MountingDIN rail (DIN35x7.5 EN50022)
Terminal typescrew or plug-in
Protection degreeIP30
Operating temperature-40 °C to +70 °C
Dimensions95 x 100 x 110 mm
Weightmax. 0.5 kg
StandardsDSTU IEC 60654-1, DSTU IEC 60654-3, DSTU IEC 60529
Example versionПНС-1-05-3-220-2: input 0–100 V, output 4–20 mA, 220 V supply, screw terminals

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

When ordering, select the input signal code (01–22) to suit the measured range: 75 mV shunt, voltage up to 500 V, or 0…5/0…20/4…20 mA current. Then choose the output signal code (1–7) to match the control system input, the supply voltage (24 V DC or 230 V AC) and the terminal type (screw or plug-in). Example: ПНС-1-05-3-220-2 — input 0–100 V, output 4–20 mA, 220 V supply, screw terminals.

Similar products

Test and measurement

Request a price and lead time

ПНС-1 — DC voltage and current to standard analogue signal converter. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.