Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

ПНС-102 — AC voltage to analogue signal converter

error 0.4 % · input 7.5 mV – 750 V · output 0–5 / 0–20 / 4–20 mA, 0–10 V · supply 187–242 V AC or 18–36 V DC

The ПНС-102 is a measuring converter that linearly transforms AC voltage into a unified analogue DC current or voltage signal. Its input, output and supply circuits are fully galvanically isolated. The unit accepts signals from 7.5–75 mV (from a shunt) up to 75–750 V. It delivers a unipolar or bipolar output of 0(-5)–5 mA, 0(-20)–20 mA, 4–20 mA or 0(-10)–10 V. Conversion error is 0.4 %, and conversion time does not exceed 6 s. The input withstands a twofold overload for no longer than 5 s. Power is supplied from 187–242 V AC mains or from an 18–36 V DC source. The 23 mm wide IP20 housing mounts on a DIN rail, with wiring made via spring terminals. Typical uses include electrical network monitoring, telemechanics and process automation in the power, metallurgical and chemical industries.

Input signal
7.5–75 mV (from shunt), Rin = 250 kΩ; 1.0–10 V, Rin = 130 kΩ; 1.5–15 V, Rin = 200 kΩ; 6–60 V, Rin = 267 kΩ; 10–100 V, Rin = 200 kΩ; 15–150 V, Rin = 667 kΩ; 25–250 V, Rin = 667 kΩ; 50–500 V, Rin = 1.3 MΩ; 75–750 V, Rin = 2.5 MΩ
Output signal
unipolar or bipolar: 0(-5)–5 mA, RL ≤ 2000 Ω; 0(-20)–20 mA, RL ≤ 500 Ω; 4–20 mA, RL ≤ 500 Ω; 0(-10)–10 V, RL > 2 kΩ
Conversion error
0.4 %
Conversion time
max. 6 s

Technical specifications

Input signal7.5–75 mV (from shunt), Rin = 250 kΩ; 1.0–10 V, Rin = 130 kΩ; 1.5–15 V, Rin = 200 kΩ; 6–60 V, Rin = 267 kΩ; 10–100 V, Rin = 200 kΩ; 15–150 V, Rin = 667 kΩ; 25–250 V, Rin = 667 kΩ; 50–500 V, Rin = 1.3 MΩ; 75–750 V, Rin = 2.5 MΩ
Output signalunipolar or bipolar: 0(-5)–5 mA, RL ≤ 2000 Ω; 0(-20)–20 mA, RL ≤ 500 Ω; 4–20 mA, RL ≤ 500 Ω; 0(-10)–10 V, RL > 2 kΩ
Conversion error0.4 %
Conversion timemax. 6 s
Overload limit2 × input signal range
Maximum overload durationmax. 5 s
Supply voltage187–242 V AC; 18–36 V DC
Consumptionmax. 5 VA (AC); max. 100 mA (DC)
Galvanic isolationfull
Connectionspring terminals
MountingDIN rail (DIN35x7,5 EN50022)
Degree of protectionIP20
Operating temperature-40 °C to +70 °C
Dimensions100 x 23 x 115 mm
Weightmax. 0.2 kg
Version exampleПНС-102-08-2-220: input 0–500 V, output 0–20 mA, 220 V AC
StandardsДСТУ EN 60529, ДСТУ2887-94, ДСТУ3272: 2011, ДСТУ2888-94, ГОСТ15150-69, EN50022

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

The version is specified by the code ПНС-102-[input]-[output]-[supply]. The input code (01–09) is selected by nominal voltage: for example, 01 for a shunt signal up to 75 mV and 08 for networks up to 500 V. The output code (1–7) defines the signal, for example 1 for 0–5 mA or 2 for 0–20 mA. The supply code specifies 220 V AC or 24 V DC.

Similar products

Test and measurement

Request a price and lead time

ПНС-102 — AC voltage to analogue signal converter. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.