ПНС-2 — AC voltage to analogue DC signal converter

input 0–75 mV … 0–750 V · output 4–20 mA, 0–20 mA, 0–5 mA, 0–10 V · error 0.4 % · supply 220 V AC / 24 V DC

The ПНС-2 is a measuring converter that linearly transforms AC voltage into a standardised analogue DC current or voltage signal. An isolating transformer separates the input from the supply, and a switching converter provides galvanic isolation between all circuits. Jumpers are used to select the input and output ranges and the conversion time. The unit handles voltages from 0–10 V up to 0–750 V, plus a 0–75 mV signal when used with a shunt. Available outputs are 0(-5)–5 mA, 0(-20)–20 mA, 4–20 mA and 0(-10)–10 V. Conversion error is 0.4 %, conversion time is no more than 6 s, and insulation withstand voltage is 2000 V. The IP 30 housing mounts on a DIN rail and operates from −40 to +70 °C. Typical applications include electrical network monitoring, telemechanics, automation of power facilities, metallurgy and the chemical industry.

Input signal / input resistance
0–75 mV (with shunt), Rin = 250 kΩ; 0–10 V, Rin = 130 kΩ; 0–15 V, Rin = 200 kΩ; 0–60 V, Rin = 267 kΩ; 0–100 V, Rin = 200 kΩ; 0–150 V, Rin = 667 kΩ; 0–250 V, Rin = 667 kΩ; 0–500 V, Rin = 1.3 MΩ; 0–750 V, Rin = 2.5 MΩ
Output signal / load
0(-5)–5 mA, RL ≤ 2000 Ω; 0(-20)–20 mA, RL ≤ 500 Ω; 4–20 mA, RL ≤ 500 Ω; 0(-10)–10 V, RL > 2 kΩ
Conversion error
0.4 %
Conversion time
not more than 6 s

Technical specifications

Input signal / input resistance0–75 mV (with shunt), Rin = 250 kΩ; 0–10 V, Rin = 130 kΩ; 0–15 V, Rin = 200 kΩ; 0–60 V, Rin = 267 kΩ; 0–100 V, Rin = 200 kΩ; 0–150 V, Rin = 667 kΩ; 0–250 V, Rin = 667 kΩ; 0–500 V, Rin = 1.3 MΩ; 0–750 V, Rin = 2.5 MΩ
Output signal / load0(-5)–5 mA, RL ≤ 2000 Ω; 0(-20)–20 mA, RL ≤ 500 Ω; 4–20 mA, RL ≤ 500 Ω; 0(-10)–10 V, RL > 2 kΩ
Conversion error0.4 %
Conversion timenot more than 6 s
Insulation resistancenot less than 4 MΩ
Insulation withstand voltage2000 V
Input overload2×, not more than 5 s
Supply voltage AC220 (+22; -33) V
Supply voltage DC24 (+4; -4) V
Power consumption ACnot more than 5 VA
Current consumption DCnot more than 120 mA
MountingDIN rail DIN35x7,5 EN50022
Ingress protectionIP 30
Operating temperature−40…+70 °C
Dimensions95 x 100 x 110 mm
Weightnot more than 0.5 kg
Example versionПНС-2-05-3-220-2: input 0–100 V, output 4–20 mA, supply 220 V AC, screw terminals
StandardsДСТУ ІЕС 60654-1, ДСТУ ІЕС 60529

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

Choose the input range according to the highest voltage to be monitored (0–10 V … 0–750 V); for 0–75 mV, use a shunt. Match the output to the receiver: 4–20 mA or 0–20 mA with loads up to 500 Ω, 0–5 mA with loads up to 2000 Ω, or 0–10 V with loads above 2 kΩ. The supply is 220 V AC or 24 V DC, and terminals are either screw or plug-in. Example: ПНС-2-05-3-220-2 (input 0–100 V, output 4–20 mA, 220 V AC, screw terminals).

Similar products

Test and measurement

Request a price and lead time

ПНС-2 — AC voltage to analogue DC signal converter. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.