Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

TEST AND MEASUREMENT

ПНС-410 — DC current and voltage converter with 4–20 mA output

4–20 mA passive output · input 0–75 mV … 0–500 V, 0–5 mA … 0–1 A · accuracy 0.25 % · 2000 V isolation

The ПНС-410 is a measuring transducer that linearly converts DC voltage or DC current into a standard 4–20 mA analogue signal. Its output is passive: the unit draws its power from the current loop, which requires an external 18–36 V supply. Input, output and supply circuits are fully galvanically isolated, with an isolation voltage of 2000 V. Depending on the version, the input accepts a 0–75 mV shunt signal, voltages up to 500 V or currents up to 1 A. Conversion error is 0.25 % of the output signal span. Conversion time is selected with jumper JP2 and is either 1–3 ms or 200–600 ms. Output load resistance is up to 500 Ω. The 76 x 26 x 115 mm housing mounts on a DIN rail, and the operating temperature range is -40 to +70 °C. Typical applications are power engineering, metallurgy, telemechanics, measuring systems and data acquisition complexes, as well as process control systems at energy-intensive industrial sites.

Output signal
4–20 mA, passive (external supply required), RL ≤ 500 Ω
ПНС-410-01
0–75 mV (from shunt), Rin = 250 kΩ
ПНС-410-02
0–10 V, Rin = 130 kΩ
ПНС-410-03
0–15 V, Rin = 200 kΩ

Technical specifications

Output signal4–20 mA, passive (external supply required), RL ≤ 500 Ω
ПНС-410-010–75 mV (from shunt), Rin = 250 kΩ
ПНС-410-020–10 V, Rin = 130 kΩ
ПНС-410-030–15 V, Rin = 200 kΩ
ПНС-410-040–60 V, Rin = 267 kΩ
ПНС-410-050–100 V, Rin = 200 kΩ
ПНС-410-060–150 V, Rin = 667 kΩ
ПНС-410-070–250 V, Rin = 667 kΩ
ПНС-410-080–500 V, Rin > 1 MΩ
ПНС-410-100–5 mA, Rin = 200 Ω
ПНС-410-110–20 mA, Rin = 50 Ω
ПНС-410-124–20 mA, Rin = 62 Ω
ПНС-410-130–1 A
Conversion time1–3 ms (jumper JP2 fitted); 200–600 ms (jumper JP2 removed)
Conversion error0.25 % of output signal span
Permissible input overloadranges up to 100 V — 5×; above 100 V — 2×
Maximum overload duration5 s max.
Supply voltage18–36 V DC (loop-powered)
Galvanic isolationfull, 2000 V
Operating temperature-40 to +70 °C
Relative humidityup to 80 %
Operating environmentenclosed non-hazardous indoor premises
Climatic/mechanical versiongroup В4 and L3 per ГОСТ 12997
Degree of protectionIP20, IP30
MountingDIN rail (EN50022)
Dimensions (HxWxD)76 x 26 x 115 mm
Weight0.13 kg max.

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

Choose the version according to the input signal. ПНС-410-01 (0–75 mV) suits current measurement via a shunt. Versions -02 to -08 cover voltage ranges from 0–10 V to 0–500 V. For current signals, use -10 (0–5 mA), -11 (0–20 mA), -12 (4–20 mA) or -13 (0–1 A). Jumper JP2 selects either fast (1–3 ms) or slow (200–600 ms) conversion.

Similar products

Test and measurement

Request a price and lead time

ПНС-410 — DC current and voltage converter with 4–20 mA output. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.