Р5018/5М — resistance box for loading instrument transformers during verification

working current 0.5–6 A · frequency 50 Hz · secondary load 1.25–50 VA · cos φ 0.8; 1

The Р5018/5М is a resistance box that acts as the secondary-circuit burden of an instrument transformer during verification in 50 Hz AC circuits. It provides a stepped series of nominal secondary load values S, expressed in volt-amperes, at a nominal power factor of either 0.8 or 1. The box's impedance has active and reactive components. Their nominal values in ohms and the limits of permissible intrinsic error in per cent are derived from calculation formulas. The working current range is 0.5–6 A. At cos φ 0.8 there are 14 load steps from 1.25 to 50 VA. At cos φ 1 there are six steps from 2.5 to 15 VA. Overall dimensions do not exceed 170 x 225 x 390 mm, and the weight is no more than 7.0 kg. The box is intended for laboratories and metrology departments that carry out verification of instrument transformers.

Purpose
load for instrument transformers during verification
Working current range
0.5–6 A
Reference frequency
50 Hz
Nominal power factor (cos φ)
0.8; 1

Technical specifications

Purposeload for instrument transformers during verification
Working current range0.5–6 A
Reference frequency50 Hz
Nominal power factor (cos φ)0.8; 1
Nominal secondary load S at cos φ 0.81.25; 2.5; 3.75; 5; 6.25; 7.5; 10; 12.5; 15; 20; 25; 30; 40; 50 VA
Nominal secondary load S at cos φ 12.5; 3.75; 5; 7.5; 10; 15 VA
Overall dimensionsmax. 170 x 225 x 390 mm
Weightmax. 7.0 kg

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

The load setting depends on the verification mode. At cos φ 0.8 the box covers the full series from 1.25 to 50 VA (14 values). At cos φ 1 only 2.5, 3.75, 5, 7.5, 10 and 15 VA are available. The current in the circuit under test must stay within 0.5–6 A.

Similar products

Test and measurement

Request a price and lead time

Р5018/5М — resistance box for loading instrument transformers during verification. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.