WR-1 — temperature and relative humidity transducer with RS-485 Modbus RTU output
Country: Ukraine · Model: WR-1
humidity 0–100 % RH · temperature -40…75 °C · accuracy ±2.0 % RH / 0.5 °C · RS-485, Modbus RTU
The WR-1 is an industrial instrument for continuous monitoring of ambient air temperature and relative humidity. It polls two independent digital sensors (DS18B20 or DHT22) and processes their signals in a microcontroller. The results are passed to a higher-level system over an RS-485 interface using the Modbus RTU protocol. Live values are shown on an OLED display, and parameters can be set up locally on the unit. Humidity is measured from 0 to 100 % RH with an accuracy of ±2.0 % RH. Temperature is measured from -40 to 75 °C with an accuracy of 0.5 °C. The scan time is up to 0.5 seconds. Two discrete outputs can be ordered for alarm or control functions based on the measured values. The relay outputs have normally open contacts rated up to 5 A. Configuration data is stored in EEPROM. The IP30 housing mounts on a DIN rail. Typical applications include ventilation and air-conditioning systems, process microclimate control, timber drying kilns and automatic control systems.
- Device type
- Humidity and temperature indicator
- Analogue inputs
- 2
- Humidity measuring range
- 0–100 % RH
- Temperature measuring range
- -40 °C to 75 °C
Technical specifications
| Device type | Humidity and temperature indicator |
|---|---|
| Analogue inputs | 2 |
| Humidity measuring range | 0–100 % RH |
| Temperature measuring range | -40 °C to 75 °C |
| Humidity accuracy | ±2.0 % RH |
| Temperature accuracy | 0.5 °C |
| Scan time | up to 0.5 s |
| Sensor types | DS18B20 / DHT22 |
| Interface | RS-485 |
| Protocol | Modbus RTU |
| USB | optional |
| Display | OLED display |
| Discrete inputs | not fitted |
| Discrete outputs | 2 (optional) |
| Output type | relay, normally open contacts (versions: relay / transistor / none) |
| Max switching voltage AC | up to 230 V |
| Max switching voltage DC | 5 to 30 V |
| Max load current | up to 5 A |
| Supply voltage | 24 V DC or 230 V AC |
| Consumption, DC supply | max. 60 mA |
| Consumption, AC supply | max. 1.5 VA |
| Non-volatile memory | EEPROM |
| Mounting | DIN rail |
| Degree of protection | IP30 |
| Operating temperature | -40 °C to +70 °C |
| Dimensions | 100 × 55 × 60 mm |
| Weight | max. 0.35 kg |
| Standards | ДСТУ IEC 60654-1:2001, ДСТУ IEC 60654-3:2001 |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
The version is defined by order codes. The sensor type can be DS18B20 or DHT22. The discrete outputs can be relay, transistor or none. A USB interface is optional and is handy for configuration. The supply voltage is either 230 V AC or 24 V DC. To switch fans or heaters, choose the relay version rated up to 5 A. For Modbus RTU data transfer only, the version without outputs is sufficient.
Similar products
Request a price and lead time
WR-1 — temperature and relative humidity transducer with RS-485 Modbus RTU output. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.