CSS — central power supply systems for emergency lighting 3–600 kVA (EN 50171)

CSS central power supply systems rated 3–600 kVA comply with EN 50171 and are built on Sentinel Tower, Sentryum and Master UPS units. They go into buildings with fire safety requirements, where they feed emergency lighting, automatic fire extinguishing, alarms, smoke extraction, CO detectors and security systems.

Models
CSS Sentinel Tower 3–5 kVA (1:1); CSS Sentryum 6–120 kVA (1-3:1, 3:3); CSS Master 100–600 kVA
Standards
EN 50171; enclosure to EN 60598-1
Overload
120 % with no time limit
Battery charging
up to 80 % of autonomy in 12 h

Technical specifications

ModelsCSS Sentinel Tower 3–5 kVA (1:1); CSS Sentryum 6–120 kVA (1-3:1, 3:3); CSS Master 100–600 kVA
StandardsEN 50171; enclosure to EN 60598-1
Overload120 % with no time limit
Battery chargingup to 80 % of autonomy in 12 h
BatteriesVRLA, AGM, GEL, vented lead-acid and nickel; batteries with a 10-year service life
Protectionbattery reverse polarity protection
Featuresdual input (CSS Sentryum, CSS Master), contact interface to EN 50171
Customs codes (for reference)
HS code8504.40
UKTZED code (Ukraine)8504403000
CN code (EU)85044095

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

The line splits into three series, CSS Sentinel Tower at 3–5 kVA (1:1), CSS Sentryum at 6–120 kVA (1-3:1 and 3:3) and CSS Master at 100–600 kVA. The system carries a 120 % overload with no time limit, so luminaire inrush when all circuits start at once does not trip it. The charger restores up to 80 % of autonomy in 12 h. It works with VRLA, AGM, GEL, vented lead-acid and nickel batteries, including those with a 10-year service life, and the battery input is protected against reverse polarity. CSS Sentryum and CSS Master have a dual input, so rectifier and bypass can run from separate feeds. The contact interface follows EN 50171 and reports status to the fire alarm panel, and the enclosure meets EN 60598-1.

How to choose

Size the power from the total of emergency luminaires and other safety loads plus margin, and let the supply decide the series. A single-phase panel in a small building is covered by CSS Sentinel Tower 3–5 kVA, and a three-phase supply with loads up to 120 kVA takes CSS Sentryum with 3:1 or 3:3 output. Large sites from 100 kVA up go to CSS Master. Autonomy and battery type come from the design, and batteries with a 10-year life cut maintenance visits.

Request a price and lead time

CSS — central power supply systems for emergency lighting 3–600 kVA (EN 50171). We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How fast does a CSS system recharge its batteries?

Up to 80 % of autonomy is restored in 12 h.

What overload can the CSS emergency lighting power system carry?

It carries a 120 % overload with no time limit.

Which standards does CSS comply with?

The systems follow EN 50171, and the enclosure complies with EN 60598-1.

How does a CSS system differ from a standard UPS?

It is built to EN 50171 for safety systems, carries 120 % overload with no time limit, recharges batteries to 80 % in 12 h and has a contact interface for fire automation.

Which batteries can a CSS system use?

VRLA, AGM, GEL, vented lead-acid and nickel types, including batteries with a 10-year life. The battery input is protected against reverse polarity.

Similar products

UPS and power supplies

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.