Futura industrial online UPS 5–800 kVA
Country: Italy · Model: Futura
The Futura industrial double-conversion UPS is available with a single-phase output of 5–50 kVA and a three-phase output of 5–800 kVA. It is installed at oil and gas facilities, in the power industry and at military sites where the load cannot tolerate an interruption of supply.
- Power
- 1-ph. output: 5–50 kVA (SRE-…/1); 3-ph. output: 5–800 kVA (SRE-5…SRE-800) per datasheet tables
- Classification
- VFI per EN 62040-3
- Output voltage
- ±1%, THD < 2%, output isolation transformer
- Efficiency
- > 92%
Technical specifications
| Power | 1-ph. output: 5–50 kVA (SRE-…/1); 3-ph. output: 5–800 kVA (SRE-5…SRE-800) per datasheet tables |
|---|---|
| Classification | VFI per EN 62040-3 |
| Output voltage | ±1%, THD < 2%, output isolation transformer |
| Efficiency | > 92% |
| Overload | 125% 10 min, 150% 1 min, 200% 0.1 s |
| Batteries | sealed lead-acid; NiCd / Li-Ion / NaNiCl2 on request |
| Protection degree | IP20 |
| Standards | EN 62040-1/-2/-3, EN 60146-1-1; NATO code (NCAGE) AD484 |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
The VFI class per EN 62040-3 means that the inverter supplies the load continuously and the output voltage does not depend on the mains voltage and frequency. Control is DSP-based, the output is held within ±1% at THD below 2%, and efficiency is above 92%. The output isolation transformer galvanically separates the load and makes the UPS tolerant of unbalanced and surge currents. The overload margin of 125% for 10 min, 150% for 1 min and 200% for 0.1 s covers motor starts and the tripping of protective devices. Several units are connected in parallel to increase power or for N+1 redundancy. Sealed lead-acid batteries are fitted as standard, with NiCd, Li-Ion or NaNiCl2 on request. The unit complies with EN 62040-1/-2/-3 and EN 60146-1-1, enclosure IP20.
How to choose
Futura power is selected from the datasheet tables; a single-phase output is available for 5–50 kVA, three-phase up to 800 kVA. The battery chemistry is chosen to suit conditions: NiCd tolerates cold and deep discharges, Li-Ion saves space. If a single-phase UPS of 2–10 kVA with built-in batteries for 20 min is needed, Mizar is simpler; for 1–3 h of autonomy up to 10 kVA there is Proton, and for substation operational DC networks the UC with a 24–400 V output is suitable.
Request a price and lead time
Futura industrial online UPS 5–800 kVA. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What does the VFI class mean for the Futura UPS?
Per EN 62040-3, VFI means double conversion, and the output voltage and frequency do not depend on the mains. Futura holds the output with ±1% accuracy and THD below 2%.
What overload does the Futura UPS withstand?
125% for 10 min, 150% for 1 min and 200% for 0.1 s.
Which batteries can be connected to Futura?
Sealed lead-acid as standard, NiCd, Li-Ion or NaNiCl2 on request.
Can several Futura UPS units be connected in parallel?
Yes, parallel operation of several units is provided; it increases power or gives redundancy in case one unit fails.
Does Futura have a NATO codification?
Yes, the Futura UPS has the NATO code (NCAGE) AD484 and complies with EN 62040-1/-2/-3 and EN 60146-1-1.
Similar products
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.