Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

UPS AND POWER SUPPLIES

Megaline — modular single-phase UPS, 1.25–10 kVA

A modular single-phase online double-conversion UPS (VFI-111) rated 1,250–10,000 VA. Power grows in 1,250 VA modules and N+X redundancy is set by module count, so the system is bought for today's load and topped up as it grows.

Power
1,250–10,000 VA (1,250 VA modules)
Topology
online, double conversion VFI-111
Redundancy
N+X
Frequency
50/60 Hz, frequency conversion

Technical specifications

Power1,250–10,000 VA (1,250 VA modules)
Topologyonline, double conversion VFI-111
RedundancyN+X
Frequency50/60 Hz, frequency conversion
BatteriesVRLA, internal or in external cabinets
Customs codes (for reference)
HS code8504.40
UKTZED code (Ukraine)8504403000
CN code (EU)85044095

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

Megaline runs on 50/60 Hz grids and can convert frequency, for example feeding a 60 Hz load from a 50 Hz supply. That matters for imported machines, test benches and marine equipment built for the other frequency. Modules are sized to the load with spares on top, and if one fails the others keep working. The VFI class means output voltage and frequency do not depend on the mains, with the inverter running all the time. VRLA batteries sit inside the case or in external cabinets, which are added when the internal batteries fall short on runtime. The module step is small, so spare capacity paid for in advance is limited to one module.

How to choose

Divide the load in VA by 1,250, round up and add one module for redundancy, which up to 10,000 VA covers a server rack or a small lab. For a 19″ server cabinet there is the rack-mount Megaline Rack. When single-phase load goes past the line's ceiling, look at TriMOD at 10–80 kW in its 3/1 configuration, taking a three-phase feed and giving one phase out.

Request a price and lead time

Megaline — modular single-phase UPS, 1.25–10 kVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

In what steps does Megaline power grow?

In 1,250 VA modules, up to 10,000 VA in one UPS including any redundant modules.

Can Megaline work as a frequency converter?

Yes, the UPS runs at 50/60 Hz and supports frequency conversion, such as 50 Hz in and 60 Hz out.

What batteries does Megaline use?

VRLA, either internal or in external cabinets, with the external ones extending runtime.

How is N+1 redundancy set up in Megaline?

Fit one more 1,250 VA module than the load needs. If any module fails, the rest keep the load running.

Similar products

UPS and power supplies

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.