UPS7700F online UPS 100–600 kVA for computer loads
Country: Japan · Model: UPS7700F
The UPS7700F series of double-conversion online UPS units rated 100–600 kVA (80–480 kW) for powering computer loads. The design is fully IGBT-based, and the input has a PWM rectifier with a power factor of at least 0.99. It is used in server rooms and data centers, banking and telecommunication systems and in industrial control systems.
- Type
- online (double conversion), fully IGBT-based
- Models
- 3/100, 3/200, 3/300, 3/400, 3/500, 3/600 (100–600 kVA / 80–480 kW)
- Input
- 380/400/415 V ±15 % (operating range 209–477 V), 50 or 60 Hz ±5 %, 3 ph, 4 wire
- Input cos φ
- ≥ 0.99
Technical specifications
| Type | online (double conversion), fully IGBT-based |
|---|---|
| Models | 3/100, 3/200, 3/300, 3/400, 3/500, 3/600 (100–600 kVA / 80–480 kW) |
| Input | 380/400/415 V ±15 % (operating range 209–477 V), 50 or 60 Hz ±5 %, 3 ph, 4 wire |
| Input cos φ | ≥ 0.99 |
| Input current harmonics | ≤ 4 % without an external filter |
| Efficiency | ≥ 94 % |
| Distortion on a rectifier load | < 5 % |
| Overload | 125 % for 10 min, 150 % for 1 min |
| Battery | 480 V (240 cells), range 400–576 V |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
The model range 3/100, 3/200, 3/300, 3/400, 3/500 and 3/600 covers 100–600 kVA. Input current harmonics do not exceed 4 % without external filters, and a high-frequency PWM inverter operates at the output. With a rectifier (non-linear) load, voltage waveform distortion is below 5 % and efficiency is 94 % and above. The input voltage is 380, 400 or 415 V with a tolerance of ±15 % (operating range 209–477 V), frequency 50 or 60 Hz ±5 %, the network is three-phase four-wire. The rated battery voltage is 480 V (240 lead-acid cells) with a range of 400–576 V. The power walk-in function is part of the standard set and smoothly transfers the load to an emergency diesel generator. The standard rectifier charges the batteries in a way that extends their service life. The number of components is reduced, and each unit goes through screening tests and a burn-in run.
How to choose
Choose by power within 100–600 kVA; the ratings go in steps of 100 kVA from 3/100 to 3/600. An overload capability of 125 % for 10 min and 150 % for 1 min covers short peaks. For fault tolerance there is synchronous no-break transfer to bypass, standby and parallel redundancy, and battery monitoring diagnoses wear and warns about replacement. If a power of 400–2500 kVA with an efficiency of 96.5 % is needed, look at the UPS7000HX-T4.
Request a price and lead time
UPS7700F online UPS 100–600 kVA for computer loads. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What power range does the UPS7700F cover?
From 100 to 600 kVA, which corresponds to 80–480 kW. There are six models, from 3/100 to 3/600.
What are the input power factor and harmonic level of the UPS7700F?
The power factor is at least 0.99, and the input current harmonic content is no more than 4 % without an external filter.
What input voltage range does the UPS7700F allow?
The nominal is 380, 400 or 415 V with a tolerance of ±15 %, operating range 209–477 V, frequency 50 or 60 Hz ±5 %. The network is three-phase four-wire.
What is the battery voltage of the UPS7700F?
The nominal is 480 V, which is 240 lead-acid cells. The permitted range is 400–576 V.
What is power walk-in in the UPS7700F?
A function of the standard set that smoothly transfers the load to an emergency diesel generator after the mains disappears.