Keor XPE — scalable UPS system, 250 kVA–2.1 MVA
Country: France · Model: Keor XPE
A scalable UPS system of up to 2.1 MVA assembled from as many as 7 power blocks of 250 or 300 kVA. Efficiency reaches 96.4 % in VFI mode and 99 % in ECO. It is installed in data centers, hospitals, industrial plants and transport facilities.
- Power
- up to 2.1 MVA (up to 7 power units of 250 or 300 kVA)
- Topology
- online, three-level IGBT, transformerless
- Efficiency
- up to 96.4 % (VFI), up to 99 % in ECO mode
- Batteries
- centralized or distributed, lithium battery compatible
Technical specifications
| Power | up to 2.1 MVA (up to 7 power units of 250 or 300 kVA) |
|---|---|
| Topology | online, three-level IGBT, transformerless |
| Efficiency | up to 96.4 % (VFI), up to 99 % in ECO mode |
| Batteries | centralized or distributed, lithium battery compatible |
| Connection | cable or busbar, top/bottom entry |
| Customs codes (for reference) | |
| HS code | 8504.40 |
| UKTZED code (Ukraine) | 8504403000 |
| CN code (EU) | 85044095 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
Keor XPE uses a transformerless online circuit on three-level IGBTs, and without an output transformer the system is lighter and needs less floor space. Power grows by adding power blocks, so the first phase of a site starts on one block and more are installed as the load grows. In VFI mode the output is independent of the mains, while ECO is used where the grid is stable and loss savings matter more. Batteries are either centralized in one room for the whole system or distributed with a set per block. Lithium batteries are also supported. Cable or busbar comes in from the top or bottom.
How to choose
Decide on the block size first, 250 or 300 kVA, as it sets the growth step and the system limit. With 300 kVA blocks, 7 of them give 2.1 MVA. Distributed batteries suit sites where a fault in one battery string must not affect the other blocks, while a centralized bank is easier to service in one room. If you need more than 2.1 MVA in one block, look at UPSaver with up to 2.67 MVA per block and 21 MVA in parallel.
Request a price and lead time
Keor XPE — scalable UPS system, 250 kVA–2.1 MVA. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
How many power blocks make up a Keor XPE system?
Up to 7 blocks of 250 or 300 kVA, for a total of up to 2.1 MVA.
What is the efficiency of Keor XPE?
Up to 96.4 % in VFI mode and up to 99 % in ECO.
Can lithium batteries be connected to Keor XPE?
Yes, the system works with lithium batteries in a centralized or distributed layout.
Does Keor XPE have a transformer?
No, the design is transformerless, with an inverter built on three-level IGBTs.
How is Keor XPE connected?
By cable or busbar, entering from the top or bottom to suit the room.