VEGA / VEGA HE — three-phase transformer-based UPS 10–800 kVA

The three-phase transformer-based VEGA and VEGA HE UPS units cover 10–800 kVA in class VFI-SS-111 under IEC EN 62040-3. They are installed in data centers, industrial processes, large buildings and medical facilities where galvanic isolation of the output is required.

Power
VEGA: 10–100 kVA (3/1), 10–200 kVA (3/3), 100–600 kVA HP with IGBT rectifier; VEGA HE: 100–800 kVA
Classification
VFI-SS-111 per IEC EN 62040-3
Inverter
with an output isolation transformer
Rectifier
6-pulse thyristor (optional 12-pulse) or IGBT with power factor correction

Technical specifications

PowerVEGA: 10–100 kVA (3/1), 10–200 kVA (3/3), 100–600 kVA HP with IGBT rectifier; VEGA HE: 100–800 kVA
ClassificationVFI-SS-111 per IEC EN 62040-3
Inverterwith an output isolation transformer
Rectifier6-pulse thyristor (optional 12-pulse) or IGBT with power factor correction
VEGA HE efficiencyup to 95.5 % online, up to 99.4 % in stand-by mode
Parallel operationup to 8 UPS units

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The inverter works into an output isolation transformer, so the load is separated from the battery circuit and the mains. The base VEGA has three configurations: 10–100 kVA with a three-phase input and a single-phase output, 10–200 kVA in a 3/3 arrangement, and the HP version of 100–600 kVA with an IGBT rectifier. The standard rectifier is a 6-pulse thyristor one, and a 12-pulse one is available to order, which reduces input current harmonics. The IGBT rectifier with power factor correction distorts the mains very little and is easier to match with a diesel generator. VEGA HE is designed for 100–800 kVA and reaches an efficiency of up to 95.5 % in online mode and up to 99.4 % in stand-by mode. Besides double conversion, the UPS works in ECO mode, as a frequency converter or as a stabilizer.

How to choose

The choice starts with the load phase count and power, then the rectifier type is determined by the requirements for input harmonics and generator compatibility. For power-hungry halls from 100 kVA, VEGA HE with higher efficiency is more cost-effective. Up to 8 UPS units are connected in parallel for N+1 redundancy or for adding power. If an isolation transformer is not needed and compactness and modularity matter, look at HELIOS-TH of 10–100 kVA with an efficiency above 95.5–96 %.

Request a price and lead time

VEGA / VEGA HE — three-phase transformer-based UPS 10–800 kVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

Why does the VEGA UPS have an output transformer?

It provides galvanic isolation of the load from the battery and the mains, which is needed for medical systems and industrial processes with sensitive grounding circuits.

What is the efficiency of the VEGA HE UPS?

Up to 95.5 % in double-conversion mode and up to 99.4 % in stand-by mode at power ratings of 100–800 kVA.

How many VEGA UPS units can be connected in parallel?

Up to 8 UPS units run in parallel for redundancy or to increase system power.

What rectifier is fitted in the VEGA UPS?

By default a 6-pulse thyristor one, optionally a 12-pulse one, and the HP version of 100–600 kVA has an IGBT rectifier with power factor correction.

Can VEGA work as a frequency converter?

Yes, besides the online mode and ECO, the UPS can be set up as a frequency converter or a voltage stabilizer.

Similar products

UPS and power supplies

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.