Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

VOLTAGE STABILIZERS

Three-phase stepped thyristor voltage stabilizers Hertz-PRO V3.0, 66–106 kW (3×100 … 3×160 A)

The Hertz-PRO V3.0 series is a high-power range of three-phase stepped voltage stabilizers with thyristor switches for production facilities, pumping stations, and large retail and administrative buildings. Models rated 3×100, 3×125 and 3×160 A provide 66, 83 and 106 kW and are available with 16 steps (2.3 % accuracy) and 36 steps (1 % accuracy). Response time to input voltage changes is 20 ms, efficiency is not less than 98 %, and the operating range extends to 100…280 V. The cabinet design, with floor-standing installation and terminal connection, is intended for long-term operation under load.

Rated current and power
3×100 A — 66 kW; 3×125 A — 83 kW; 3×160 A — 106 kW
Number of steps
16 or 36
Stabilization accuracy
2.3 % (16 steps); 1 % (36 steps)
Dimensions, max.
1280×384×779 mm

Technical specifications

Rated current and power3×100 A — 66 kW; 3×125 A — 83 kW; 3×160 A — 106 kW
Number of steps16 or 36
Stabilization accuracy2.3 % (16 steps); 1 % (36 steps)
Dimensions, max.1280×384×779 mm
Conductor cross-section per phase16 / 16 / 25 mm² (min.), up to 40 mm² (max.)
Switch typethyristor
Efficiencynot less than 98 %
Output voltage220 V per phase
Stabilization range within stated accuracy150–260 V
Cut-off thresholdsUmin 100 V, Umax 280 V
Response time20 ms
Mains frequency45–65 Hz
Lower cut-off threshold adjustment60–135 V
Output voltage adjustment200–230 V
Coolingforced, 2 two-speed fans
Degree of protectionIP20
Climatic versionУХЛ, category 4.2
No-load power20 W per phase

Analogues in the catalogue

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Main features: thyristor step switching, 20 ms; 16 or 36 steps; mechanical bypass (transit); phase synchronization in incomplete-phase operation; network analyzer with measurement of current and input power; protection against short circuit, overload, overheating and overvoltage (varistors at input and output); input and output chokes against RF interference.

Technical data: Rated current and power — 3×100 A — 66 kW; 3×125 A — 83 kW; 3×160 A — 106 kW; Number of steps — 16 or 36; Stabilization accuracy — 2.3 % (16 steps); 1 % (36 steps); Dimensions, max. — 1280×384×779 mm; Conductor cross-section per phase — 16 / 16 / 25 mm² (min.), up to 40 mm² (max.); Switch type — thyristor; Efficiency — not less than 98 %; Output voltage — 220 V per phase; Stabilization range within stated accuracy — 150–260 V; Cut-off thresholds — Umin 100 V, Umax 280 V; Response time — 20 ms; Mains frequency — 45–65 Hz; Lower cut-off threshold adjustment — 60–135 V; Output voltage adjustment — 200–230 V; Cooling — forced, 2 two-speed fans; Degree of protection — IP20; Climatic version — УХЛ, category 4.2; No-load power — 20 W per phase.

Application: large workshops and production lines; pumping and compressor stations; server rooms, medical institutions and shopping complexes; facilities with generators of proportionate power.

How to choose

We select the power rating, version and configuration to suit the load; delivery time and warranty terms are to be confirmed with the manager.

Similar products

Voltage stabilizers

Request a price and lead time

Three-phase stepped thyristor voltage stabilizers Hertz-PRO V3.0, 66–106 kW (3×100 … 3×160 A). We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.