EV Charger Business — 2×22 kW EV charging station
Country: Germany · Model: EV Charger Business
The EV Charger Business commercial AC charging station has 2 Type 2 charging points, each delivering up to 22 kW at up to 32 A from a 230 / 400 V three-phase supply. It goes into company parking lots where fleet cars and staff EVs charge at the same time.
- Charging points
- 2, Type 2
- Power
- up to 22 kW per point
- Interfaces
- RFID, OCPP
- Mounting
- wall or floor-standing
Technical specifications
| Charging points | 2, Type 2 |
|---|---|
| Power | up to 22 kW per point |
| Interfaces | RFID, OCPP |
| Mounting | wall or floor-standing |
| More from the manufacturer’s documentation | |
| Versions | with 2 Type 2 sockets or 2 Type 2 cables, 6 m; version compliant with German calibration law (MessEG) |
| Nominal voltage | 230 / 400 V AC |
| Frequency | 50 Hz |
| Current per charging point | up to 32 A |
| Charging mode | Mode 3 per IEC 61851-1 |
| Communication | Ethernet RJ-45, OCPP 1.6 JSON, EEBUS; 4G modem (MessEG version) |
| Protection per charging point | 6 mA DC residual current detection; 4-pole 40 / 0.03 A type A RCD |
| External circuit breaker | C 32 A, 3-pole per cable |
| Operating temperature | −25 °C to +40 °C |
| Storage temperature | −30 °C to +70 °C |
| Degree of protection / impact resistance | IP54 / IK08 |
| Protection class / overvoltage category | I / III |
| Relative humidity | 5–90% |
| Installation altitude | 0–2,000 m |
| Dimensions (W × H × D) | 409 × 490 × 176 mm / 430 × 490 × 176 mm |
| Weight | 13.5 kg / 21 kg |
| Connection | NYY-J up to 5 × 10 mm²; TN, TN-S, TT grids |
| Energy meter | integrated, MID-compatible |
| Load management | dynamic charging load control |
| System compatibility | The manufacturer eMobility Portal, Data Manager M |
| Standards | IEC 61851-1:2019 |
| Charging stand (optional) | one-sided 565 × 1,421.5 × 435 mm, 42.5 kg; two-sided 40 kg, load up to 80 kg |
| Customs codes (for reference) | |
| HS code | 8537.10 |
| UKTZED code (Ukraine) | 8537109890 |
| CN code (EU) | 85371098 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
Charging runs in Mode 3 per IEC 61851-1:2019, and the station comes with 2 Type 2 sockets or 2 tethered 6 m Type 2 cables. Users authorize with RFID cards, and the unit talks to billing over OCPP 1.6 JSON via Ethernet RJ-45, plus EEBUS. A built-in MID-compatible meter supplies data for energy billing. Each point has 6 mA DC leakage detection and a 4-pole 40 / 0.03 A type A RCD. The NYY-J feeder can be up to 5 × 10 mm², on TN, TN-S and TT grids. The IP54 / IK08 housing weighs 13.5 or 21 kg depending on version, is rated for −25 °C to +40 °C and hangs on a wall or stands on a floor pedestal. Within the commercial energy system, it works with Data Manager M to match charging power to on-site solar output and load.
How to choose
First check spare capacity at the service entrance. With several stations, turn on dynamic charging load control so the cars share the available current and the main breaker stays closed. The version with 6 m cables suits shared parking where drivers arrive without their own cable. The MessEG version with a 4G modem follows the German calibration law, for sites that bill energy on verified metering. For one car at a private home charging from PV, the wall-mounted eCharger fits better.
Request a price and lead time
EV Charger Business — 2×22 kW EV charging station. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What is the charging power of the EV Charger Business?
Up to 22 kW on each of the 2 charging points, at 400 V and up to 32 A.
Does the EV Charger Business support OCPP?
Yes, it runs OCPP 1.6 JSON and accepts RFID cards, so it connects to third-party billing.
What connector does the EV Charger Business use?
Both points are Type 2, either as Type 2 sockets or as 6 m Type 2 cables.
What breaker goes upstream of the EV Charger Business?
A 3-pole C 32 A breaker per feeder cable. The type A RCD and 6 mA DC leakage detection are already inside the station.