Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

UPS AND POWER SUPPLIES

Master Industrial — industrial UPS 30–80 kVA with 220 V DC bus

The Master Industrial UPS at 30–80 kVA runs on a 220 V DC battery bus and is built for vibration, mechanical stress and dust. It is used in manufacturing, petrochemicals, power distribution networks and power plants. The output is single-phase from a three-phase input, so the unit feeds auxiliary panels and automation.

Power
30, 40, 60, 80 kVA
Input/output
3:1
Topology
online, VFI-SS-111, input and output isolation transformers
Battery
220 V DC (108–114 cells)

Technical specifications

Power30, 40, 60, 80 kVA
Input/output3:1
Topologyonline, VFI-SS-111, input and output isolation transformers
Battery220 V DC (108–114 cells)
Short-circuit current3×In
Coolingredundant ventilation with monitoring of each fan
Customs codes (for reference)
HS code8504.40
UKTZED code (Ukraine)8504403000
CN code (EU)85044095

Ukrainian replacement/analogue

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

Ratings are 30, 40, 60 and 80 kVA with a 3:1 input/output layout. The VFI-SS-111 online topology adds input and output isolation transformers, so noise from plant drives passes neither into the load nor back into the grid. The battery is built from 108–114 cells, the count chosen for the battery type and end-of-discharge voltage. Short-circuit current is 3×In, which helps trip a feeder breaker selectively without the UPS going to bypass. Cooling is redundant with each fan monitored separately, so one fan failure does not stop the unit. The Easy Source and Battery Care functions match those of the Master MPS series.

How to choose

Pick the rating from the panel's single-phase load with inrush margin, out of 30, 40, 60 and 80 kVA. Master Industrial fits where isolation, fault current and dust matter. For a three-phase load, or parallel redundancy of up to 8 units, the Master MPS at 10–200 kVA in 3:3 is the better fit, and from 100 kVA up the Master HP.

Request a price and lead time

Master Industrial — industrial UPS 30–80 kVA with 220 V DC bus. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What battery voltage does the Master Industrial UPS use?

220 V DC, from a battery of 108–114 cells.

What short-circuit current does the Master Industrial deliver?

Short-circuit current is 3×In.

Which ratings does the Master Industrial series offer?

30, 40, 60 and 80 kVA, 3:1 input/output.

Why does an industrial UPS need input and output transformers?

They isolate the load, battery and grid galvanically, keeping plant noise away from the automation. In Master Industrial both transformers are part of the VFI-SS-111 design.

What happens if a fan fails in the Master Industrial?

Cooling is redundant, so the UPS keeps running, and per-fan monitoring flags the fault at once.

Similar products

UPS and power supplies

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.