Three-phase UPS Volter UPS DPH 20–120 kW (online, double conversion)

Three-phase UPS Volter UPS of the DPH series work online with double conversion and are made for 20, 40, 60 and 120 kW. Transfer from mains to battery takes 0 ms and the output is a sine wave. They are installed in server rooms, telecom nodes, on production lines and in building services.

Models
DPH31 20K; DPH33 40K; DPH33 60K; DPH33 120K (power 20 / 40 / 60 / 120 kW)
Type
online, three-phase (4 wires with earth)
40K model data: input
190–520 V at half load; 305–478 V at full load
40K model data: output
380/400/415 V ± 1 %

Technical specifications

ModelsDPH31 20K; DPH33 40K; DPH33 60K; DPH33 120K (power 20 / 40 / 60 / 120 kW)
Typeonline, three-phase (4 wires with earth)
40K model data: input190–520 V at half load; 305–478 V at full load
40K model data: output380/400/415 V ± 1 %
40K model data: efficiency94 %
40K model data: batteriesup to 32 pcs; charging current up to 12 A
40K model data: dimensions and weight845×300×1010 mm (D×W×H), 61 kg
Mountingfloor
Temperature+5…+30 °C

Analogues in the catalogue

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The models DPH31 20K, DPH33 40K, DPH33 60K and DPH33 120K are three-phase with 4 wires and earth, floor-mounted, for +5…+30 °C. For the 40K model the input is 190–520 V at half load and 305–478 V at full load, the output is 380/400/415 V ± 1 % and efficiency is 94 %. Up to 32 batteries with a charging current of up to 12 A connect to this model, and it measures 845×300×1010 mm (D×W×H) and weighs 61 kg. The UPS holds an overload of 100–110 % for 10 min and 110–130 % for 1 min. Low harmonic distortion of the output sine wave is kept in any mains condition.

How to choose

Choose the power from 20, 40, 60 and 120 kW and size the battery string from the 40K data, up to 32 batteries. The 20 kW unit is DPH31 20K, and the 40, 60 and 120 kW units are DPH33. For a smaller series, look at the Volter UPS rated 30 kVA (27 kW) and 40 kVA (33 kW) with a 384 V battery. European analogues in the catalogue cover 10–120 kVA and the 6000 series. Supplied as the official representative in Ukraine.

Request a price and lead time

Three-phase UPS Volter UPS DPH 20–120 kW (online, double conversion), Volter. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How many batteries connect to the 40 kW DPH UPS?

Up to 32 batteries with a charging current of up to 12 A connect to the 40K model.

What is the transfer time to batteries in the DPH UPS?

The mains-to-battery transfer time is 0 ms, so the supply is not interrupted.

What overload can the DPH UPS carry and for how long?

An overload of 100–110 % is allowed for 10 min and 110–130 % for 1 min.

What are the output voltage accuracy and efficiency of the 40K model?

The 380/400/415 V output is held within ± 1 % and efficiency is 94 %.

Similar products

UPS and power supplies

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.